Mobile Dehumidifier 
 

Operation 

Technology 

Spare Parts 

Edition GB – M02 

REMKO - powerful like a bear. 

Summary of Contents for ETF 300

Page 1: ...REMKO ETF 300 550 Mobile Dehumidifier Operation Technology Spare Parts Edition GB M02 REMKO powerful like a bear...

Page 2: ......

Page 3: ...ating Instructions Mobile Dehumidifier REMKO ETF 300 550 G Always keep these operating instructions near or on the unit G Contents page Air Dehumidification 4 Safety Instructions 6 Unit Description 6...

Page 4: ...kg of dry air absolute water content 1 m of air weighs approx 1 2 kg at 20 C Depending on the temperature each kg of air can only absorb a defined quantity of water vapour When this quantity has been...

Page 5: ...n the other hand energy is re leased when gas is liquefied and this energy is called condensation heat The energy rate of evaporation and condensation heat is identical For water this is 2250 kJ kg 4...

Page 6: ...the unit Do not cover the unit during operation Make sure not to transport the unit during operation Avoid strong vibrations on the unit as soon as there is condensate in the condensate tank Make sure...

Page 7: ...h a feeler which has been mounted between the evapora tor lamellas When the formation of hair frost on the evaporator increases its heat absorption capacity is re duced due to the insulating character...

Page 8: ...ng into and going out of the room should be avoided if possible You can obtain better air circulation if you place the unit at a height of approx 1 m 1 Introduce the main plug into a prop erly protect...

Page 9: ...e slightly and remove it pulling towards and downwards Then remove the dust filter Slight o insignificant dirt is to be cleaned by blowing out or vacuum cleaning the dust filter carefully If the dust...

Page 10: ...from 3 C to 32 C Control air humidity Min 40 relative humidity Check hygrostat setting and set a lower value if nec essary Check whether dust filter is dirty if so clean it Check whether the evaporat...

Page 11: ...30 50 Rated current consumption max A 3 8 Power consumption max kW 0 82 Power consumption at 20 C 70 r h kW 0 60 Fuse protection required A 16 Sound pressure level LpA 1m 1 dB A 59 Dimensions total de...

Page 12: ...e reserve the right to make modifications in dimensions and construction in the interests of technical progress 18 08 02 1 2 3 4 5 6 7 8 56 15 16 17 19 20 25 26 27 28 29 40 35 36 37 38 41 30 42 43 44...

Page 13: ...26 solenoid valve 1104470 27 defrosting thermostat incl sensor 1104471 28 micro switch 1104472 29 electric cable 1101320 30 cable relief 1104562 35 axle 1104474 36 wheel 1102155 37 wheel lock ring 11...

Page 14: ...14 We reserve the right to make modifications in dimensions and construction in the interests of technical progress Exploded View ETF 550...

Page 15: ...hermostat incl sensor 1104471 18 micro switch 1104472 19 electric cable 1101320 20 cable relief 1104473 21 axle 1104509 22 wheel 1102155 23 wheel lock ring 1101622 24 wheel cap 1101623 26 starting cap...

Page 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...