8
Starting
The unit is automatically switched on if the humidity rate
in the room is higher than the previously set valve.
The unit operates fully automatically until the prese-
lected relative air humidity has been reached or until the
unit has been switched off by the floater in the conden-
sate tank.
In such a case the yellow control lamp “condensate tank
full” is lit up.
Operation with Hygrostat
The REMKO hygrostat (accessory) is supplied with a
special intermediate plug.
1. Insert intermediate plug into a properly protected
plug socket.
2. Position hygrostat in an adequate place within the
room to be dehumidified.
Not directly near the unit.
Installation
◊
Install the unit in a horizontal position to ensure the
trouble-free drainage of condensate.
◊
Install the unit in the middle of the room, if possible,
to ensure optimal air circulation.
◊
If this is not possible due to the conditions in the
building make sure that the air can be easily sucked
in at the front of the unit and blown off from its rear
part.
◊
Make sure to observe a minimum distance of 50 cm
◊
Do not install the unit directly near radiators
or other heat sources.
◊
Make sure to keep the room to be dried and
dehumidified closed, so that air from outside cannot
penetrate into it.
◊
Entering into and going out of the room should be
avoided if possible.
◊
You can obtain better air circulation if you place the
unit at a height of approx. 1 m.
1. Introduce the main plug into a prop-
erly protected plug socket.
230V/1~ 50 Hz / fuse 16 A
2. Put main switch into position „I”.
Green control lamp “operation” is lit
up.
Important Hints for the installation:
◊
Connection cable extensions may only be used
when they have been completely unrolled.
◊
The lock cover in front of the condensate tank have
to be closed correctly (tender spot).
G
The filter of the unit is to be controlled and
cleaned thoroughly before every use. If the air
suction grille is dirty, please cleaned it up like
shown in chapter ”Maintenance and Service”.
3. Connect the unit plug with the
intermediate plug.
4. Put main switch of the unit into
position “I”.
5. Preselect the desired humidity
by setting the hygrostat.
Important Hints!
◊
Make sure that appropriate measures for mainte-
nance and care are taken when the unit is installed
in dusty surroundings as well as in stables with am-
moniacal atmosphere
See chapter “Maintenance and Care”.
◊
The electrical connection of the unit is to be carried
out according to DIN VDE 0100, part 704. It is to be
connected to service entrances with residual current
operated device.
◊
If the unit is installed in washhouses, showers or
similar wet areas the user has to protect it by an ade-
quate residual current operated device according to
the relevant regulations.
Summary of Contents for ETF 300
Page 2: ......