background image

10

REMKO ETF 320

Adjusting the discharge 
direction

The dehumidified room air is 
discharged on the top of the unit. 
The pivotable air flap [S] is used to 
adjust the discharge direction. 

Press the air flap’s rear surface [D] 
to open it. 

The front folds upwards. The air 
direction can be adjusted infinitely. 

The following notes must also be 
observed in full: 

   If possible, open the air flap 

completely to direct the air flow 
upwards 

   Ensure that the air can 

discharge without hindrances 

This is the only way to 
guarantee optimum unit 
operation!

 

   Ensure that sensitive objects 

such as house plants are not 
placed directly in the air flow 
emerging from the unit

D

S

Automatic defrost system 

The moisture contained in the 
room air condenses when cooling 
and coats the evaporator fins 
with rime or ice depending on the 
air temperature and the relative 
humidity (% RH). 

The automatic defrost system that 
is integrated in the unit switches 
the defrost cycle on if required. 

The rime or ice that has 
accumulated on the exchanger 
surfaces is defrosted using heat gas 
as required. 

This defrosting method is 
particularly fast and effective, and 
guarantees high dehumidification 
performance.

Dehumidification mode is only 
paused for a short time during the 
defrost phase. 

The “Defrost mode” indicator light 
indicates that the defrost cycle is 
running. 

NOTE

If the room temperature is 
sufficiently high, the surface 
of the fins will not be cold 
enough for rime formation to 
occur, rendering defrosting 
unnecessary.  
Therefore, the air dehumidifier 
works economically.

 

Adjusting units/moisture

The unit’s dehumidification power 
is entirely dependent on the 
conditions inside the room, the 
room temperature, the relative 
humidity and observance of the 
notes in the “Setting up”chapter. 

The higher the room temperature 
and relative air humidity, 
the higher the dehumidification 
power. 

A relative humidity of around 
45 to 60 % is sufficient in living 
rooms. The air humidity should not 
exceed 40 to 45 % in warehouses, 
archives, etc. 

Adjust the hygrostat 
for the recommended 
air humidity  
in living rooms. 

Approx. 50 %.

Adjust the hygrostat 
for the recommended 
air humidity 
in archives. 

Approx. 40 %. 

Adjust the hygrostat 
for the minimum 
air humidity in the 
installation room. 

The units work in continuous 
operation in this position!

NOTE

The maximum possible 
dehumidification power is only 
obtained when the air flap is 
opened completely.

s

s

s

Summary of Contents for ETF 320

Page 1: ...Edition GB I03 REMKO ETF 320 Mobile dehumidifiers Operation Technology Spare parts...

Page 2: ......

Page 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Air dehumidification 4 Safety notes 6 Unit description 7 Set up 8 Commissioning 9 Shutdown 11 Unit transpo...

Page 4: ...r vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of pain...

Page 5: ...emperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The d...

Page 6: ...t on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture The units have been subjected to extensive material function...

Page 7: ...xtinguishes again when the empty condensate container is re inserted The units then restart after a switch on delay of around 3 minutes In unattended continuous operation with an external condensate c...

Page 8: ...if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the surrounding atmosphere Avoid having opened windows and doors etc and avoid frequent entry...

Page 9: ...a waiting time of 3 minutes has elapsed Restart protection NOTE The devices can be switched ON and OFF via an external time accessory if required Before commissioning the unit or if local requirements...

Page 10: ...rly fast and effective and guarantees high dehumidification performance Dehumidification mode is only paused for a short time during the defrost phase The Defrost mode indicator light indicates that t...

Page 11: ...the connection nozzle that is now exposed In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan buck...

Page 12: ...utlet grille for contamination on a regular basis Clean or replace if required Care and maintenance NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of...

Page 13: ...ax 40 C soap solution Finally always rinse the filter carefully with clear water and allow to dry 7 Also check the intake grill for contamination and clean if necessary 8 Before refitting grill and fi...

Page 14: ...tutory or locally applicable regulations The unit is loud or condensate runs out Check whether the unit is on a stable and even base Check whether the unit is standing upright and stably Have the cond...

Page 15: ...are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose o...

Page 16: ...it We reserve the right to modify the dimensions and design as part of the ongoing technical development process 1 3 6 5 10 29 27 34 24 19 16 15 40 41 43 17 18 26 28 39 9 25 7 35 36 32 23 30 33 21 31...

Page 17: ...1103673 20 Fan motor 1103661 21 Fan housing 1111133 22 Fan wheel 1103636 23 Protection grid 1103637 24 Condenser fan motor 1103668 25 Distribution block 1111134 26 Mains cable with plug 1103660 27 Boa...

Page 18: ...Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3...

Page 19: ...15 2 At 15 C 60 RH l day 8 4 Max airflow volume m3 h 190 Condensate container capacity Litres 5 5 4 5 Refrigerant 1 R 410A Refrigerant quantity g 180 Power supply V 230 1 Frequency Hz 50 Max rated cur...

Page 20: ...dvisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on...

Reviews: