14
REMKO ETF 320
The unit runs but condensate
is not formed:
■
Check the room temperature
The operating range of the unit
is between 6 °C and 32 °C
■
Check the humidity of the air
Min. 40 % RH required
■
Check the intake grill and air
filter for contamination
Clean or replace if required!
■
Have the heat exchanger fins
checked for contamination
This work requires the unit to
be opened and must therefore
only be carried out by an
authorised specialist company!
Electrical wiring diagram
NOTE
If the unit fails to function
correctly after the checks have
been carried out, contact an
authorised specialist.
Note
on refrigerants
The units work with
environmentally-friendly
and ozone-neutral R410a
refrigerant.
The mixture of refrigerant
and oil within the unit must
be disposed of properly
in accordance with the
statutory or locally-applicable
regulations.
The unit is loud or
condensate runs out:
■
Check whether the unit is on
a stable and even base
■
Check whether the unit is
standing upright and stably
■
Have the condensate trap or
the connection nozzles checked
to see whether there are dirt
deposits on them
This work requires the unit to
be opened and must therefore
only be carried out by an
authorised specialist company!
s
s
s
P3
P4
P5
P2
P6
P1
CN 4
CN 3
CN 2
CN
5
T3.15AL 250V
Kontrollleuchten
Hygrostat
Mikro-
schalter
Frostschutz-
sensor
ROT
ROT
BLAU
B
LA
U
BLAU
BLAU
BLAU
W
E
IS
S
Kondensator
BLAU
BRAUN
GRÜN/
GELB
PE
23
0V
/5
0H
z
N
L
Ventilator-
motor
Kondensator
W
E
IS
S
B
LA
C
K
K
om
pr
es
so
r
2-Wege
Magnet-
ventil
Work on the refrigerant
system and on the electrical
equipment must only be
conducted by a specially-
authorised specialist!
!
CAUTION
RED
BLUE
BLUE
BLUE
BLUE
BLUE
BROWN
GREEN/
YELLOW
WHITE
BLACK
2-way
solenoid
valve
Fan motor
Microswitch
Antifreeze
sensor
Hygrostat
Indicator lights
Condenser
Condenser
Compressor