background image

4

REMKO ETF 320

It is evident that the corrosion 
rate below 50 % relative humidity 
(RH) is low, and below 40 % is 
negligible. 
 
The corrosion rate increases 
significantly above 60 % RH. 
This threshold for damage as the 
result of humidity also applies to 
other materials, such as powdery 
substances, packaging, wood and 
electronic units.

Buildings may be dried in a variety 
of ways:

1.  

By heating and air exchange:

   The air in the room is heated 

in order for moisture to be 
removed and then this air is fed 
outside. All of the energy that 
is involved is lost together with 
the moist air that is released.

2.  

By air dehumidification:

   The moist air that is present 

within an enclosed space is 
continuously dehumidified 
according to the condensation 
principle.

The correlations occurring when 
air is dehumidified are based on 
physical laws.  
These are depicted here in 
graphical form in order to provide 
you with a brief overview of the 
principles of air dehumidification.

The use of REMKO 
air dehumidifiers

  Even if windows and doors 

are well insulated, water and 
moisture are still capable of 
penetrating thick concrete walls.

  The water required for setting

when producing concrete, 
mortar and plaster etc. may only 
be diffused after 1-2 months.

  Even moisture trapped in the 

masonry after a flood is released 
very slowly.

  The same is also true of 

moisture contained in stored 
materials for example.

The moisture (water vapour) 
released from parts of a building 
or materials is absorbed by the 
surrounding air. As a result, the 
moisture content increases, which 
ultimately gives rise to corrosion, 
mould, rot, peeling of paint and 
other unwanted damage.

By way of example, the diagram 
shows the corrosion rate of metal 
in different levels of humidity.

A

ir dehumidif

ication

With regard to energy 
consumption, air dehumidification 
has one distinct advantage: 

Energy expenditure is limited 
exclusively to the air volumes 
present. The mechanical heat that 
is released by the dehumidification 
process is fed back into the room. 

Under normal use, the air 
dehumidifier uses approximately 
25 % of the energy that is 
required for the “heating and 
ventilating” principle.

Relative air humidity

Our ambient air is a gaseous 
mixture which always contains 
a certain volume of water in the 
form of water vapour. This volume 
of water is specified in g per kg of 
dry air (absolute moisture content). 

1 m

3

 of air weighs approx. 1.2 kg 

at 20 °C

Depending on the temperature, 
each kg of air is only capable of 
absorbing a certain volume of 
water vapour. Once this capacity 
has been reached, the air is 
referred to as “saturated” and has 
a relative humidity (RH) of 100 %. 

Relative humidity is understood 
to mean the ratio between the 
current quantity of water vapour in 
the air and the maximum possible 
quantity of water vapour at the 
same temperature. 

The ability of the air to absorb 
water vapour increases as 
the temperature rises. I.e. the 
maximum possible (absolute) 
water content becomes greater as 
the temperature rises.

Corr

osion speed

Rel. humidity %

Summary of Contents for ETF 320

Page 1: ...Edition GB I03 REMKO ETF 320 Mobile dehumidifiers Operation Technology Spare parts...

Page 2: ......

Page 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Air dehumidification 4 Safety notes 6 Unit description 7 Set up 8 Commissioning 9 Shutdown 11 Unit transpo...

Page 4: ...r vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of pain...

Page 5: ...emperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The d...

Page 6: ...t on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture The units have been subjected to extensive material function...

Page 7: ...xtinguishes again when the empty condensate container is re inserted The units then restart after a switch on delay of around 3 minutes In unattended continuous operation with an external condensate c...

Page 8: ...if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the surrounding atmosphere Avoid having opened windows and doors etc and avoid frequent entry...

Page 9: ...a waiting time of 3 minutes has elapsed Restart protection NOTE The devices can be switched ON and OFF via an external time accessory if required Before commissioning the unit or if local requirements...

Page 10: ...rly fast and effective and guarantees high dehumidification performance Dehumidification mode is only paused for a short time during the defrost phase The Defrost mode indicator light indicates that t...

Page 11: ...the connection nozzle that is now exposed In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan buck...

Page 12: ...utlet grille for contamination on a regular basis Clean or replace if required Care and maintenance NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of...

Page 13: ...ax 40 C soap solution Finally always rinse the filter carefully with clear water and allow to dry 7 Also check the intake grill for contamination and clean if necessary 8 Before refitting grill and fi...

Page 14: ...tutory or locally applicable regulations The unit is loud or condensate runs out Check whether the unit is on a stable and even base Check whether the unit is standing upright and stably Have the cond...

Page 15: ...are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose o...

Page 16: ...it We reserve the right to modify the dimensions and design as part of the ongoing technical development process 1 3 6 5 10 29 27 34 24 19 16 15 40 41 43 17 18 26 28 39 9 25 7 35 36 32 23 30 33 21 31...

Page 17: ...1103673 20 Fan motor 1103661 21 Fan housing 1111133 22 Fan wheel 1103636 23 Protection grid 1103637 24 Condenser fan motor 1103668 25 Distribution block 1111134 26 Mains cable with plug 1103660 27 Boa...

Page 18: ...Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3...

Page 19: ...15 2 At 15 C 60 RH l day 8 4 Max airflow volume m3 h 190 Condensate container capacity Litres 5 5 4 5 Refrigerant 1 R 410A Refrigerant quantity g 180 Power supply V 230 1 Frequency Hz 50 Max rated cur...

Page 20: ...dvisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on...

Reviews: