background image

5

Water vapour 
condensation

Because the capacity for the 
maximum possible volume of 
water vapour increases as the air 
is heated, the volume of water 
vapour contained remains constant 
and so relative humidity falls.

In contrast, because the capacity 
for the maximum possible volume 
of water vapour decreases as the 
air is cooled, the volume of water 
vapour contained remains constant 
and so relative humidity increases.
If the temperature continues to 
fall, the capacity for the maximum 
possible volume of water vapour 
is reduced so much so that it is 
ultimately equal to the volume of 
water vapour contained in the air.  
This temperature is referred to 
as the dew point. If the air is 
cooled to below the dew point, 
the volume of water vapour in 
the air will become greater than 
the maximum possible volume of 
water vapour.
At this point, the water vapour 
begins to precipitate.
This condenses to water and 
moisture is removed from the air.

Examples of condensation include 
steamed-up window panes in 
winter, or the moisture on the 
outside of a cold drinks bottle.

As the relative humidity of the air 
increases, so too does the dew 
point, making it easier for the 
temperature to fall below it.

Building materials and structures 
are capable of absorbing 
considerable volumes of water, 
such as brick 90-190 l/m³, heavy 
concrete 140-190 l/m³ and 
limestone 180-270 l/m³. 
The drying of moist materials such 
as masonry is effected as follows:

■   

The moisture 
moves from  
the inside of the  
material to its 
surface

   Evaporation occurs on the 

surface = Transfer of water 
vapour to the ambient air

   The air containing water vapour 

is constantly circulated through 
the REMKO air dehumidifier. 
The air is dehumidified and, 
slightly heated, leaves the unit 
in order to re-absorb water 
vapour

   In this way, the moisture 

contained in the material is 
reduced gradually 

The material is dried!

The accumulated condensate is 
collected in the unit and drained 
off from there.

Drying materials

Verdampfer

Kondensator

°C

30

25

20

15

% r.F.

100

90
80
70
60
50
40
30
20
10

+

+

-

Lufttemperatur

Luftfeuchte

Verlauf

Luftrichtung

As it flows through or over the evaporator, the air stream is cooled 
to dew point. The water vapour condenses, and is collected 
in a condensate trap from where it is drained off.

Temp.

Water vapour content in g/m

3

 at humidity of

°C

40 %

60 %

80 %

100 %

-5

1.3

1.9

2.6

3.3

+10

3.8

5.6

7.5

9.4

+15

5.1

7.7

10.2

12.8

+20

6.9

10.4

13.8

17.3

+25

9.2

13.8

18.4

23.0

+30

12.9

18.2

24.3

30.3

Condenser

Evaporator

% RH

Air temperature

Air direction

Air humidity

Progression

Summary of Contents for ETF 320

Page 1: ...Edition GB I03 REMKO ETF 320 Mobile dehumidifiers Operation Technology Spare parts...

Page 2: ......

Page 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Air dehumidification 4 Safety notes 6 Unit description 7 Set up 8 Commissioning 9 Shutdown 11 Unit transpo...

Page 4: ...r vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of pain...

Page 5: ...emperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The d...

Page 6: ...t on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture The units have been subjected to extensive material function...

Page 7: ...xtinguishes again when the empty condensate container is re inserted The units then restart after a switch on delay of around 3 minutes In unattended continuous operation with an external condensate c...

Page 8: ...if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the surrounding atmosphere Avoid having opened windows and doors etc and avoid frequent entry...

Page 9: ...a waiting time of 3 minutes has elapsed Restart protection NOTE The devices can be switched ON and OFF via an external time accessory if required Before commissioning the unit or if local requirements...

Page 10: ...rly fast and effective and guarantees high dehumidification performance Dehumidification mode is only paused for a short time during the defrost phase The Defrost mode indicator light indicates that t...

Page 11: ...the connection nozzle that is now exposed In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan buck...

Page 12: ...utlet grille for contamination on a regular basis Clean or replace if required Care and maintenance NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of...

Page 13: ...ax 40 C soap solution Finally always rinse the filter carefully with clear water and allow to dry 7 Also check the intake grill for contamination and clean if necessary 8 Before refitting grill and fi...

Page 14: ...tutory or locally applicable regulations The unit is loud or condensate runs out Check whether the unit is on a stable and even base Check whether the unit is standing upright and stably Have the cond...

Page 15: ...are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose o...

Page 16: ...it We reserve the right to modify the dimensions and design as part of the ongoing technical development process 1 3 6 5 10 29 27 34 24 19 16 15 40 41 43 17 18 26 28 39 9 25 7 35 36 32 23 30 33 21 31...

Page 17: ...1103673 20 Fan motor 1103661 21 Fan housing 1111133 22 Fan wheel 1103636 23 Protection grid 1103637 24 Condenser fan motor 1103668 25 Distribution block 1111134 26 Mains cable with plug 1103660 27 Boa...

Page 18: ...Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3...

Page 19: ...15 2 At 15 C 60 RH l day 8 4 Max airflow volume m3 h 190 Condensate container capacity Litres 5 5 4 5 Refrigerant 1 R 410A Refrigerant quantity g 180 Power supply V 230 1 Frequency Hz 50 Max rated cur...

Page 20: ...dvisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on...

Reviews: