background image

9

Commissioning the units

1.  Turn the hygrostat’s 

rotary knob 
anticlockwise into 
the “OFF” position. 

2.  Connect the unit's 

electrical connection 
to a properly 
installed mains 
socket. 

3.  Open the air flap on the top 

of the unit.

4.  Preselect the 

desired air humidity 
for the installation 
room on the 
hygrostat. 

 The recommended approximate 
setting values are listed in the 
adjacent section. 

Commissioning

Control panel

The hygrostat’s rotary knob and 
the indicator lights are located on 
the control panel. 

  

Hygrostat

 

The infinitely adjustable 
hygrostat can be used to select 
the required air humidity in the 
installation room. 

  

“Dehumidification” indicator 
light 

This light indicates that 
the unit is operating correctly. 

  

“Container full” indicator light

This light indicates that the 
condensate container is full and 
must be emptied. 

  

“Defrost mode” indicator light

 

This light indicates that the 
automatic defrost system that 
is integrated in the unit has 
switched on the defrost cycle. 

NOTE

In room temperatures below 

10 °C

 and relative humidity 

below 

40 %

, economical use 

of the unit can no longer be 
guaranteed.

NOTE

Note that the compressor does 
not switch on until a waiting 
time of 3 minutes has elapsed.

Restart protection!

 

NOTE

The devices can be switched 
ON and OFF via an external 
time (accessory) if required.  

Before commissioning the unit 
or if local requirements dictate, 
the air-inlet grill and air-outlet 
grill must be checked for 
contamination.

Important notes prior 
to commissioning 

   All extensions to the electrical 

connection must be of 
a sufficient cable size and must 
only be used fully rolled out or 
unrolled

   Never use the mains cable 

as a pull cord 

   After being switched on, 

the units operate fully-
automatically until switched off 
by the hygrostat or float when 
the condensate container is full 

   The condensate container must 

be inserted properly  

The unit cannot be operated if 
the condensate container is not 
inserted properly!

   In order to prevent damage to 

the condenser, the units are 
equipped with a mechanism 
that prevents the compressor 
being immediately switched 
back on after it is switched off 

The units do not switch back 
on until a waiting time of 
around 3 minutes has elapsed!

   If the units work in continuous

operation with an external 
condensate drainage 
connection, refer to the 
relevant section

NOTE

A contaminated grille or filter 
must be cleaned or replaced 
immediately.

s

s

s

The units are only permitted 
to be operated with the air 
flap open in order to prevent 
overheating.

 

!

   CAUTION

Summary of Contents for ETF 320

Page 1: ...Edition GB I03 REMKO ETF 320 Mobile dehumidifiers Operation Technology Spare parts...

Page 2: ......

Page 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Air dehumidification 4 Safety notes 6 Unit description 7 Set up 8 Commissioning 9 Shutdown 11 Unit transpo...

Page 4: ...r vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of pain...

Page 5: ...emperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The d...

Page 6: ...t on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture The units have been subjected to extensive material function...

Page 7: ...xtinguishes again when the empty condensate container is re inserted The units then restart after a switch on delay of around 3 minutes In unattended continuous operation with an external condensate c...

Page 8: ...if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the surrounding atmosphere Avoid having opened windows and doors etc and avoid frequent entry...

Page 9: ...a waiting time of 3 minutes has elapsed Restart protection NOTE The devices can be switched ON and OFF via an external time accessory if required Before commissioning the unit or if local requirements...

Page 10: ...rly fast and effective and guarantees high dehumidification performance Dehumidification mode is only paused for a short time during the defrost phase The Defrost mode indicator light indicates that t...

Page 11: ...the connection nozzle that is now exposed In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan buck...

Page 12: ...utlet grille for contamination on a regular basis Clean or replace if required Care and maintenance NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of...

Page 13: ...ax 40 C soap solution Finally always rinse the filter carefully with clear water and allow to dry 7 Also check the intake grill for contamination and clean if necessary 8 Before refitting grill and fi...

Page 14: ...tutory or locally applicable regulations The unit is loud or condensate runs out Check whether the unit is on a stable and even base Check whether the unit is standing upright and stably Have the cond...

Page 15: ...are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose o...

Page 16: ...it We reserve the right to modify the dimensions and design as part of the ongoing technical development process 1 3 6 5 10 29 27 34 24 19 16 15 40 41 43 17 18 26 28 39 9 25 7 35 36 32 23 30 33 21 31...

Page 17: ...1103673 20 Fan motor 1103661 21 Fan housing 1111133 22 Fan wheel 1103636 23 Protection grid 1103637 24 Condenser fan motor 1103668 25 Distribution block 1111134 26 Mains cable with plug 1103660 27 Boa...

Page 18: ...Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3...

Page 19: ...15 2 At 15 C 60 RH l day 8 4 Max airflow volume m3 h 190 Condensate container capacity Litres 5 5 4 5 Refrigerant 1 R 410A Refrigerant quantity g 180 Power supply V 230 1 Frequency Hz 50 Max rated cur...

Page 20: ...dvisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on...

Reviews: