Starting the unit
1. Move the operating
switch [2] to the "0"
(off) position.
2. Connect the unit's
power plug to a
properly installed
and fused mains
socket. Connect
220-240 V/50 Hz.
3. Move the operating
switch [2] to the “I”
(on) position.
4. The green “in operation”
indicator light will illuminate
and the unit will operate in fully-
automatic dehumidification
mode.
Before commissioning the unit or if
local requirements dictate,
the air-inlet grill and air-outlet
grill must be checked for
contamination.
Important notes
prior to commissioning
■
All extensions to the electrical
connection must be of a
sufficient cable size and must
only be used fully rolled out
or unrolled
■
Never use the mains cable
as a pull cord
■
After being switched on,
the units operate fully-
automatically until switched
off by the float when
the condensate container is full
■
The condensate container
must be inserted properly and
the sealing flap must be locked
Commissioning
Operation and indicators
1
2
3
4
1 = Operating hours counter
2 = Operating switch
3 = GREEN indicator light
“Operation”
4 = YELLOW indicator light
“Container full”
Operation with a humidity switch
The REMKO humidity switch
(accessories) is supplied with
a special adapter.
The following procedure must be
followed when commissioning
units in conjunction with a
humidity switch:
1. Insert the adapter into a
properly fused mains socket.
2. Place the humidity switch
in a suitable location within
the room being dehumidified.
Not in the immediate vicinity
of the units or sources of heat.
3. Insert the power plug (or a cable
extension) into the adapter.
4. Set the desired air humidity on
the humidity switch.
5. Move the operating switch [2]
on the unit to position "I".
The units will switch on
automatically when the air
humidity in the room exceeds
the pre-set level on the humidity
switch.
The units will now operate fully-
automatically until the desired
relative humidity (% RH) has
been reached or until the unit is
switched off by the float when
the condensate container is full.
In the event that this occurs,
the yellow
“Container full”
control
lamp will illuminate.
NOTE
A contaminated grille or filter
must be cleaned or replaced
immediately.
NOTE
In room temperatures below
10°C
and relative humidity
below
40%
, economical use
of the unit can no longer be
guaranteed.
NOTE
The units are only fully
functional if the condensate
container is inserted properly.
16
REMKO ETF Eco Series