background image

  The contained refrigerant R290 is 

colourless and odourless.

  The unit must not be stored or 

operated in rooms which have a 
room area of 10 m

(ETF 500 Eco) 

or 12 m

(ETF 600 Eco)

 

or less.

  The accumulation of refrigerant 

due to leakages can lead to a fire 
and explosions in rooms which 
are too small due to the develop-
ment of heat or ignition sources.

  The units must be stored care-

fully. Mechanical damage must 
be avoided.

  Intervention in the refrigeration 

circuit may only be done by certi-
fied specialist personnel taking 
into account the safety notes of 
the manufacturer.

  Maintenance and repairs may 

only be carried out by authorised 
personnel which have the cor-
responding knowledge in regards 
to flammable refrigerant.

Do not use anything other than 

the agent recommended by the 

manufacturer to speed up a 

possible defrosting process or to 

clean the units. The unit may only 

be operated and stored in rooms 

where there are no devices with 

potential ignition sources. Do 

not go below the minimum room 

area of 10 m

(ETF 500 Eco) or 

12 m

(ETF 600 Eco). Note that 

leaking refrigerant is colourless 

and odourless.

The unit must not be burned or 

pierced!

 

!

   WARNING!

Safety instructions for the 

operator

The operational safety of the units 
and components is only assured 
providing they are used as intended 
and in a fully assembled state.

  This unit may only be installed 

and operated as described in this 
manual.

  Independent conversion and/or 

modification of any kind is strictly 
prohibited.

  Children must not be left unsu-

pervised when close to the unit.

  For safety reasons, people with 

mental, physical or other health 
limitations must not operate this 
unit unattended.

  The unit is not permitted to be 

operated with damaged cables. 
The unit must be repaired by a 
specialist immediately.

  The unit may only be operated 

via a power supply with ground-
ing.

  The use of extension cables is not 

recommended.

  The air filter must be cleaned 

at intervals of no more than 2 
weeks.

  The unit is not permitted to be 

operated in the vicinity of heat 
sources.

  The unit must be transported up-

right. Residue from the conden-
sate must be drained off before 
transport. 

  Operating the units in rooms with 

potential ignition sources (naked 
flames, gas or electrical heaters, 
fireplaces) is prohibited.

  The unit may only be installed, 

operated and stored in rooms 
larger than 10 m

(ETF 500 Eco) 

or 12 m

(ETF 600 Eco).

  Protective covers (grilles) over 

moving parts must not be 
removed from units that are in 
operation.

  Do not operate units or compo-

nents with obvious defects or 
signs of damage.

  Contact with equipment parts or 

components can lead to burns or 
injury.

  The units and components must 

not be exposed to any mechani-
cal load, extreme levels of humid-
ity or extreme temperatures.

  Never drill through the housing 

cover or have the unit come into 
contact with fire.

  Rooms in which refrigerant may 

escape must be adequately aer-
ated and ventilated. Otherwise 
there is danger of suffocation.

  All housing parts and unit open-

ings, e.g. air inlets and outlets, 
must be free from foreign objects, 
fluids or gases.

  Do not leave the units running 

for an extended period unsuper-
vised.

UImproper use can cause serious 
damage to the unit.
Read this manual carefully before 
commissioning!

8

REMKO ETF Eco Series

Summary of Contents for ETF 500 Eco

Page 1: ...Operating and installation instructions Edition EN X02 Read the instructions prior to performing any task ETF 500 Eco ETF 600 Eco REMKO ETF Eco series Mobile air dehumidifiers...

Page 2: ......

Page 3: ...to modifications No liability accepted for errors or misprints Air dehumidification 4 6 Safety notes 6 12 Intended use 13 Customer service and guarantee 13 Environmental protection and recycling 13 Un...

Page 4: ...leased from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of paint and other...

Page 5: ...condenses and is collected in a condensate trap from where it is drained off Drying materials Water vapour condensation Because the capacity for the maximum possible volume of water vapour increases a...

Page 6: ...s its moisture Safety notes General safety notes Carefully read the manual before commissioning the units or their components for the first time It provides useful tips and notes such as hazard warnin...

Page 7: ...An unobstructed air inlet and air outlet must be guaranteed at all times The air inlet grille must always be kept free of dirt and loose objects The units must not be covered during operation The unit...

Page 8: ...close to the unit For safety reasons people with mental physical or other health limitations must not operate this unit unattended The unit is not permitted to be operated with damaged cables The unit...

Page 9: ...t all times Work may only be car ried out by authorised specialist personnel with knowledge of handling combustible refriger ants Prepare the work area Any persons present must be informed about the r...

Page 10: ...e guaranteed again If the defect on the spare part cannot be remedied and downtime of the unit is no longer acceptable an adequate temporary solution must be arranged The owner operator of the unit mu...

Page 11: ...refrigerant or if possible the affected part disconnected from the system using stopcocks The affected system parts must be flushed with oxygen free nitrogen run before and during the repair work Emp...

Page 12: ...ant Transportation of units which contain combustible refriger ants National provisions must be observed Storing of units which contain combustible refrigerant National provisions must be observed Tra...

Page 13: ...packaging materials are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Ther...

Page 14: ...ough for rime formation to occur rendering defrosting unnecessary Therefore the air dehumidifiers work economically The cooled and dehumidified air is re heated by the condenser heat exchanger and blo...

Page 15: ...ources of heat Air circulation is improved if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the neighbouring atmosphere Avoid having opened wind...

Page 16: ...on with a humidity switch The REMKO humidity switch accessories is supplied with a special adapter The following procedure must be followed when commissioning units in conjunction with a humidity swit...

Page 17: ...dehumidification mode The unit will switch off and the yellow indicator light will illuminate To empty the condensate container the following procedure must be followed 1 Move the operating switch 2 t...

Page 18: ...er 3 If moisture remains on the evaporator or water remains in the condensate container the units must only be transported in an upright position 5 Drain the condensate into a lower level drain To ope...

Page 19: ...y be operated with the dust filter in place Observe the regular care and maintenance intervals In accordance with the operating conditions the units must if necessary be checked at least yearly by a s...

Page 20: ...for ice or rime formation If ice has formed check the functionality of the automatic defrost and the temperature sensor Check whether or not the evaporator temperature is below room temperature If thi...

Page 21: ...iner full H2 Control lamp green in operation K1 Time relay t 30 min M1 Compressor motor M2 Fan motor P1 Operating hours counter S1 Operating switch S2 Microswitch float S3 Defrost thermostat Y1 Defros...

Page 22: ...imensions and design as part of the ongoing technical development process Exploded view of ETF 500 600 Eco 4 5 6 8 10 11 12 13 14 15 2 1 16 17 20 21 26 27 22 25 30 29 32 33 35 34 37 36 23 23 7 24 18 3...

Page 23: ...Socket for time relay 16 Condenser cpl 17 Solenoid valve On request by providing 18 Defrost thermostat with probe the serial number 19 Microswitch 20 Mains cable with plug 21 Cable passage with strain...

Page 24: ...gnature 19 Date Signature 20 Date Signature Comments Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned outside Unit cleaned inside Fan blade cleaned Fan housing cle...

Page 25: ...0 Max rated current consumption A 2 71 2 90 Max power consumption kW 0 62 0 67 At 20 C 70 RH kW 0 49 0 50 Specific energy consumpt SEC max kWh l 0 31 0 26 At 20 C 70 RH kWh l 0 26 0 20 Electrical prot...

Page 26: ...26 REMKO ETF Eco Series...

Page 27: ...27...

Page 28: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews: