10
REMKO HTL 80/170
Control panel
1
2
9
8
7
6
5
1 = Thermostat receptacle
2 = Strapping plug
5 = Operating switch
6 = Indicator light "gREEN"
"Operation"
7 = Indicator light "RED"
"Burner fault"
8 = Reset button "Burner"
9 = Mains cable with plug
Heating without room
thermostat
The units are operating in
permanent operating mode.
1. Connect the strapping
plug supplied [2] with
the thermostat receptacle [1]
on the unit.
2. Move the operating
switch to the "I" (on)
position.
2
1
Commissioning
One person, who has been
adequately trained in the handling
of the unit, should be tasked with
the operation and monitoring
of the unit.
Connecting the units with
the electrical power supply
The electrical connection is made
using a built-in mains cable with
plug.
1. Move the operating
switch to the "0" (off)
position.
2.
Connect the power plug
with a properly installed and
appropriately safeguarded
mains socket
230V or shock-proof
400V/3~N/50Hz .
3. Open all of the oil supply shut-off
devices.
With the initial commissioning,
air in the lines can lead to a fault
shut-down of the burner
.
s
s
s
Paraffin formation with low
outside temperatures
Even at low outside temperatures
it is necessary to ensure that there
is an adequate supply of heating
oil that is capable of flowing.
■
Paraffin formation can start with
temperatures as high as 5 °C
■
To avoid this appropriate
preventative measures must be
implemented.
e.g.
Winter-proof EL heating
oil or winter Diesel, heated oil
tank, insulated oil lines etc.
■
Note that fault-free operation
of the Multiflex oil pre-heating
can only be guaranteed if
the unit has been supplied
with electrical power for a long
period of time before starting
■
It is not possible to rectify
paraffin separation that
has already occurred with
the heating. If paraffin has
already formed it is necessary
to clean out the complete fuel
system
nOTE
The 400V version of the unit
is equipped with a device
for automatically checking
the turning direction of the fan
motor, as standard.
nOTE
The electrical connection
for the units must be made
at a separate feedpoint with
a residual current device in
accordance with VDE 0100,
Section 55.
ATTEnTiOn
All cable extensions must only
be used in fully un-reeled or
reeled off condition.
nOTE
Paraffin formation can start
with temperatures as high
as 5 °C. To avoid this
appropriate preventative
measures must be
implemented, e.g. winter
Diesel.