In the “Thermoreg. Unit” field, use the arrow keys
to select the window for the setpoint in nominal or
energy-saving mode and press the “Enter” key.
1 x
!
Thermoreg. Unit B01
Heat pump temperature
Nominal setpoint (ON)
Cooling: 23.0 C
°
Heating: 0.0 C
°
The value can now be changed using the two
arrow keys.
!
Thermoreg. Unit B01
Heat pump temperature
Nominal setpoint (ON)
Cooling: 9.0 C
°
Heating: 0.0 C
°
Press the “Enter” key to confirm your selection.
1 x
!
Thermoreg. Unit B01
Heat pump temperature
Nominal setpoint (ON)
Cooling: 9.0 C
°
Heating: 0.0 C
°
The setting is now made and saved.
Display and acknowledge malfunctions
In order to protect the unit from damage, the con-
troller checks the components that are relevant for
the safety of the unit by means of sensors for tem-
perature, pressure, configuration, etc.
An error code and a brief description of the mal-
function are displayed in the error view of the con-
troller. A rectified error can be acknowledged in the
error view:
!
12:22 19/02/18 Unit:01
Outside T: - --- C
°
System T: 1 9.5 C
°
STATUS:
Alarm-Off
To enter the error view, press the “Alarm” key on
the start screen.
1 x
!
!
Alarms ALF01
Position: ID1
Fan overload
An active malfunction is now displayed in the alarm
menu. After eliminating the cause of the error,
acknowledge the malfunction by pressing the
“Alarm” key twice.
2 x
!
!
Thermoreg. Unit B01
Heat pump temperature
Nominal setpoint (ON)
Cooling: 23.0 C
°
Heating: 0.0 C
°
Unit
Alarms ALF01
No active alarm
Press ENTER
to DATA LOGGER
The malfunction is now acknowledged. The last 50
malfunctions can be found in the error memory for
subsequent review.
REMKO KWE
30