External enabling configuration
With the use of a normally open contact as an
external contact, a controller parameter must be
reconfigured. The parameter “Id08” must be
switched from “NC” to “NO”. If this does not
happen, the controller does not recognise the
external contact as a normally closed contact. The
“Id08” parameter can be changed in the “I/O Con-
figuration” menu item. The following program
sequence must be programmed.
!
12:22 19/02/18 Unit:01
Outside T: - --- C
°
System T: 1 9.5 C
°
STATUS:
Off
Call up the main menu.
1 x
!
Main menu 8/8
F.Board switch
G.Service
H.Manufacturer
Select the following submenu:
+
!
Manufacturer menu 2/5
b.I/O Configuration
c.Factory settings
a.Configuration
Open the window “b . I/O Configuration”.
+
Password entry
Enter the 4-digit password.
+
x 4
!
I/O Config. Hb04
Digital inputs
ID07
ID08
Remote On/Off: NC
General alarm:
N
C
Set the alarm contact.
+
!
I/O Config. Hb04
Digital inputs
ID07
ID08
General alarm: NO
Remote On/Off:
N
C
Set the external enabling contact.
+
!
I/O Config. Hb04
Digital inputs
ID07
ID08
General alarm: NO
Remote On/Off:
N
O
This completes the configuration.
47