Malfunction indicated by flashing code RVD 684-1054 DC
Error description
Number
of flashes
per
second)
1)
LED timer
2)
Error
code
3)
EEPROM error, indoor unit
1
OFF
E0
Communication error between indoor unit and outdoor unit
2
OFF
E1
Evaporator fan motor speed control not OK
4
OFF
E3
Room air temperature probe faulty
5
OFF
E4
Evaporator temperature probe faulty
6
OFF
E5
No cooling capacity after 30 minutes
7
OFF
EC
Condensate pump liquid level switch triggered
8
OFF
EE
Safety shut-down due to increased power consumption
1
ON
F0
Outdoor unit air inlet temperature probe faulty
2
ON
F1
Condenser outlet temperature probe faulty
3
ON
F2
Temperature probe for heat gas line faulty
4
ON
F3
EEPROM error, outdoor unit
5
ON
F4
Condenser fan speed control not OK
6
ON
F5
Temperature probe suction pipe in outdoor unit faulty
7
ON
F6
Inverter error
1
FLASHES
P0
Over/undervoltage error
2
FLASHES
P1
Safety shut-down compressor excess temperature
3
FLASHES
P2
Safety shut-down due to low outside temperature
4
FLASHES
P3
Compressor control faulty
5
FLASHES
P4
Mode conflict
6
FLASHES
P5
Low pressure alarm
7
FLASHES
P6
1)
LED [1] in the bottom figure
2)
LED [2] in the bottom figure
3)
LED [3] in the bottom figure
2
1
3
FUNC
Fig. 61: Malfunction indicated by flashing code RVD 684-1054 DC