Installation inside buildings
n
Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts,
adjoining rooms or halls (Fig. 30).
n
Install an additional fan with a rated flow com-
parative to that of the outdoor unit being
installed in the room and which can compen-
sate any additional pressure loss in ventilation
n
Comply with any regulations and conditions
affecting the statics of the building. If neces-
sary, fit acoustic installation.
2
1
K
3
W
3
Fig. 30: Installation inside buildings
K: Cold fresh air
W: Warm air
1: Outdoor unit
2: Additional fan
3: Air shaft
5.5 Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air
distribution.
1000
1000
E
C
B
A
D
2
1
1000
1000
1000
IT
AT
Fig. 31: Minimum clearances, indoor unit and outdoor unit (all measurements in mm)
AT: Outdoor unit / IT: Indoor unit
1: Air inlet / 2: Air outlet
A
B
C
D
E
RVD 354-1054 DC
300
2000
600
300
600
REMKO RVD series
28