Legend:
HYG = Hygrostat
M 1 = Compressor
M 2 = Fan motor 1
M 3 = Fan motor 2
M 4 = Fan motor 3
Y 1 = Solenoid valve
R3.1 = Condenser sensor
R3.2 = Evaporator sensor
Electrical wiring diagram
R3.1
R3.2
HYG
L1 N
230V
50 Hz
M 1
M
1~
M
1~
M 2
Y 1
Test
M
1~
M
1~
M 4
M 3
AMB.
NTC
COND.
NTC
EVAP.
NTC
PRES.
THA
WAT.
SENS
HYG
TH.
STAT
FAN
MAINS
FAN
COMPR.
VALVE
HEAT
Fan motors:
SLN 40 = Motor M2
SLN 60 = Motor M2 and M3
SLN 80 = Motor M2 M3 and M4
Constant ventilation:
If constant air circulation is re-
quired, i.e. independent of de-
humidification, a jumper can be
connected between terminals
25
and 26
.
The fan or fans then operate with-
out any control and monitoring in
a continuous mode.
External hygrostat:
Recommended for frequent hu-
midity variation is the installation
of an external hygrostat which is
available as an accessory.
Disconnect the integrated hygro-
stat at terminals
21 and 22
.
Install the external hygrostat at a
suitable location in the room to
be dehumidified and connect to
terminals
21 and 22
.
The output voltage on terminals
21 and 22
is
12V
.
NOTE
Only authorised specialists
may install and carry out
maintenance work on the
units!
Electronic control board
NOTE
A disconnector switch should
be installed in the supply con-
nection at a suitable and easily
accessible location.
ATTENTION
Prior to carrying out mainte-
nance or repairs, the unit must
always be disconnected from
the supply.
We reserve the right to make dimensional and design changes in the interest of technical advances.
SLN 40 - SLN 80
14
REMKO SLN 40-80