Before commissioning the unit
or if local requirements dictate,
the air-inlet grill and air-outlet
grill must be checked for
contamination.
The units are operated using
an integrated hygrostat that is set
to 60 % RH (default value for spas
and indoor swimming pools)
.
If the room humidity is below
60 % RH, the unit does not start.
If the relative humidity is
above 60 %, the unit starts
the dehumidification process
automatically.
If you would like to make changes
to the hygrostat settings, remove
the front housing cover and
the control board cover located
in the upper section in order
to access the control board.
Commissioning
NOTE
When the unit is switched on
or off using the main switch,
a signal is issued upon startup
and the LED display lights
up blue as soon as the unit
is ready for operation. Once
all conditions have been met,
the dehumidifying process
begins.
Display and operator panel
The display is a four-digit seven
segment display. The first two
digits are used to display the
respective “code”, e.g. rHXX, for
setting the room humidity and
the last two digits correspond
to the value set.
In the standard view, no code is
shown on the display. It is only
the value of the humidity currently
measured that is displayed.
The operator panel with
the buttons “Up”, “Down” and
“OK” can be found on the right-
hand side of the front of the
control board. These can be used
to navigate around the menu
structure of the control board and
to couple the control board with
a wireless remote control.
NOTE
If the air humidity is lower
that the set value, the unit will
not start up, even if the mains
voltage is connected.
Control board, front
Control board
The units are equipped with
an electronic controller.
This features various interfaces and
a display. The following section
describes these features in detail.
Code
Value
NOTE
Interrupting the operation
of the unit before
the compressor has run for
6 minutes will activate a restart
lock lasting approx. 4 minutes.
EXT RH/T
These terminals allow you to
connect up an external electronic
humidity and temperature probe.
The temperature probe must
be an NTC probe with 10 k
Ω
at 25 °C and a B25/85 of 3969
K. The humidity probe must be
designed for a voltage supply of
12 V DC and feature an analogue
voltage output of 0-10
_
V with
max. 10 mA.
ALARM
The alarm contacts are two
potential-free contacts that are
open in an unswitched state.
The RUN contact is closed when
the compressor is in operation.
The FAIL contact is closed when
there is a malfunction in the unit.
12VDC
Relays can be controlled via
the HEAT contacts in order to
switch the external heating on
and off. They are active when
the °C option in the menu is set to
a value.
USB interface
The information on the USB interface
can be found further on in this manual.
RS-485 interface
The information on the RS-485
interface can be found further
on in this manual.
13