16
REMKO VRS EN Series
Heating mode
The units operate fully
automatically and in accordance
with the room temperature.
1. Switch on the local main switch
or fuse(s)/breaker(s).
2. Open the fuel supply.
3. Set the desired temperature on
the room thermostat.
4. Switch the "Heating" selector
switch.
It should be noted that the fan
burner switches on immediately
when heat is required, but the
supply air fan is only switched on
automatically after the setpoint
temperature has been reached.
This prevents the unwanted
blowing out of cold air.
Move the two selector switches to
the “0” position.
The supply air fan continues to run
to cool down the heat exchanger
and may start several times until it
is finally switched off.
For longer periods of inactivity,
the units should be disconnected
from the mains and the fuel supply
shut off.
Shutdown
Ventilation
1. Turn the "Ventilate" selector
switch.
In this switch position, the supply
air fan runs permanently.
The units can be used for air
recirculation or ventilation
purposes.
Thermostatic control is not
possible.
■
The burner must be set to
optimum values in accordance
with the manufacturer's
specifications, but at least to
those of the federal emission
control act
■
A measurement report must be
generated and handed over to
the operator for safekeeping
■
The operator must be familiarised
with the operation of the system
■
The specialist contractor
declarationand the contractor
certificate of the respective
installation company carrying
out the work must be submitted
to the responsible authorities.
CAUTION
The unit may never be switched
off via the main switch or an
emergency switch prior to
the completion of the cool-down
phase (except in emergencies).
NOTE
If the units are not set to their
nominal heat load (see name
plate) or if the design is too
large for the required heat
demand, the burners operate
in cycle mode.
Cycle operation can
significantly reduce
the efficiency of the
equipment and the life of
the components.
0
1
0
1
0
1
CAUTION
Before commissioning,
the operating instructions for
the burner must be observed!
For setting values, please refer
to the respective instructions!
!