The units may only be operated by persons who 
have received proper training in their operation. 

   

The units must be installed and operated in such a 
way that people are not exposed to radiant heat and 
fires cannot occur. 

   

The units may only be installed and operated in 
closed rooms where the units have adequate air 
supply for combustion. 

 

If this cannot be guaranteed, a separate burner-
driven device that sucks in fresh air from the outside 
must be installed. 

   

The units may only be set up on a non-flammable 
surface. 

   

The units may only be attached to non-flammable, 
sturdy structures or ceilings made from the materials 
with sufficient load-bearing capacity. 

   

The units are to be attached with sturdy mounts 
which are fixed on the unit.

 

   

The units may not be set up or operated in surround-
ings susceptible to fire or explosions. 

   

The units must be set up outside of traffic zones,    
e.g. away from cranes. 

   

A safety zone of 1 m is to be maintained around the 
units.

 

   

The protective air suction grille must always be kept 
free of dirt and loose objects. 

   

Never insert foreign objects into the units.

 

   

Do not expose the units to a direct stream of water.

 

   

Never let water get inside the units. 

   

All of the units’ electrical cords are to be protected 
from damage (e.g. caused by animals, etc.).

 

   

Do not bypass or block safety mechanisms while 
the unit is in operation.

 

Safety Instructions 

 

Make sure to observe relevant local building and fire 
protection codes and abide by professional association  
regulations when the units are in operation! 

   

Before performing any maintenance or repair work, 
make sure to unplug the units from the power supply! 

Remove fuses or switch off the customer-supplied 
main switch.

 

 

It is not sufficient to switch off the units with the 
operating switch! 

The units are designed for exclusive use with 1-speed  
fan/burner operation. 

The units are operated with a separate forced-air oil 
burner. 

It is essential to connect the units to an exhaust system 
approved by the state building authorities. 

The units are equipped with a 1-speed radial fan with 
drive motor that runs quietly and requires little mainte-
nance as well as attached switching and regulating units. 

The units meet the basic safety and health require-
ments found in the relevant EU regulations. They are 
safe and easy to operate. 

The robust design and clean processing of these high-
quality units ensure a long service life and smooth op-
eration. They can also be assembled quickly, easily and 
affordably and are easy to service.

 

REMKO automatic heaters supply heat or regulate the 
temperature of: 

   

Workshops 

   

Warehouses 

   

Exhibition spaces 

   

Trade show spaces 

   

Temporary structures for warehousing 

   

Showrooms 

   

Greenhouses etc. 

Operating Locations of the Units 

The units are direct-fired devices that supply instanta-
neous heat. They are only used for industrial and com-
mercial purposes. There are generally no restrictions as 
to where they can be used.

 

Description of the Unit

 

 

The units (automatic heaters) have been designed for 
universal, fully-automatic and smooth operation. They 
are fired directly with heating oil or diesel.

 

Operation

 

After switching on the unit by setting the operating 
switch to “Heizen” (heating), the forced-air burner turns 
on automatically. 

he green “burner“ operating light is illuminated on the 
control panel for monitoring purposes. The combustion 
chamber with heat-exchanger now heats up until the 
target temperature is reached. 

After the burner has run for a short time, the temperature 
control thermostat “TR” (rated

 

temperature 35 to 40 °C) 

automatically switches the air supply fan on. Warm air 
is blown out. 

The combustion chamber with heat-exchanger is 
heated up until the target temperature of the tempera-
ture monitor (TW) is reached.

 

Proper Use 

The units have been designed and equipped exclu-
sively for industrial and commercial heating and ventila-
tion purposes. 

The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are 
made to the units. 

Summary of Contents for WKL 20 INOX

Page 1: ...REMKO powerful like a bear REMKO WKL 20 INOX Oil compact heating system Edition GB P11 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...Oil Burner Assembly 16 Initial Operation 16 Service and Guarantee 17 Maintenance Log 18 Stationary Warm Air Heating System REMKO WKL 20 INOX Read these instructions carefully before setting up operati...

Page 4: ...connect the units to an exhaust system approved by the state building authorities The units are equipped with a 1 speed radial fan with drive motor that runs quietly and requires little mainte nance a...

Page 5: ...bend the capillary tubes near to solder points When installing the capillary tubes be careful not to damage or bend them too sharply The sensors may only be mounted in the mounting brackets supplied b...

Page 6: ...tup room but not close to hazardous areas Air Supply for Combustion An adequate supply of air for combustion must be en sured by meeting the relevant building requirements Excerpts from the German fir...

Page 7: ...e units the regional provisions and regulations must be observed The units may only be operated with accessories that have either been approved by the manufacturer or sup plied with the units Proceed...

Page 8: ...f the burner sup plied by the manufacturer If burners from other manufacturers are used they must be checked for compatibility with the unit Fan Motor Connection The units are completely wired at the...

Page 9: ...If the unit is not set to its rated heat load or it is too large for the necessary heat requirements the burner only runs in cyclical operation Because the required operating temperature is not reache...

Page 10: ...er Combustion residue in the com bustion chamber and in the heat exchanger must be removed Parts that wear out e g flue gas brakes oil nozzles oil filter inserts seals etc must be checked cleaned and...

Page 11: ...and capillary pipes of the safety temperature limiter STB and the temperature moni tor TW for damage and ensure that the sensor has been properly positioned Check whether the red control light burner...

Page 12: ...max unit without burner kW 0 17 Power consumption max for manufacturer supplied burner kW 0 28 Sound pressure level LpA 1m without burner dB A 58 Waste gas connection mm 130 Weight Unit without burne...

Page 13: ...ture limiter TH Optional Room thermostat or day night regulator TR Fan control thermostat TW Temperature monitor WS Wieland plug We reserve the right to make modifications in dimensions and constructi...

Page 14: ...Exploded View 4 1 2 5 3 13 8 9 12 11 7 3 4 10 16 15 20 18 19 17 21 22 23 26 25 27 14 24 6 We reserve the right to make modifications in dimensions and construction in the interests of technical progre...

Page 15: ...ction grille 289109 16 Fan cpl 1108606 17 Seal for inspection cover 1103156 18 Inspection cover with waste gas connection 1103155 19 Waste gas suppressor set 6 piece 1103157 20 Fan control thermostat...

Page 16: ...manually but not so that they are completely tight initially The sliding flange still has to be tightened 4 Push the flame pipe into the burner chamber until it clicks into place 5 Connect the flame p...

Page 17: ...the guarantee to be valid the customer must com pletely fill out the guarantee certificate enclosed with all heating units and send it back to REMKO GmbH Co KG in a timely manner after purchasing of t...

Page 18: ...damage Maintenance burner Test run Model Model No Burner Burner No Maintenance work may only be performed by authorised personnel settings must comply with legal specifications A corresponding test lo...

Page 19: ......

Page 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606 260 E Mail info remko de Internet www remko de...

Reviews: