19
Appendix A: FAQ (Frequently asked questions)
Sometimes, the PV system does not work normally; we recommend the following solutions for average
troubleshooting. This can help the technician to understand the problem and take a proper action.
Fault
LCD display
Possible actions
Clearable Fault
Isolation Fault1
Isolation Fault2
1. Check whether the inverter is earthed and test impedance
between PV (+) & (-) and the impedance must exceed
3MΩ;
2. Check whether the AC-side has contacts with earth.
Grid Faults:
10min OVR
Fault OVR
Fault UVR
Fault OFR
Fault UFR
1. Wait for 5 minutes, if the grid returns to normal, PV inverter
automatically restarts.
2. Make sure grid voltage and frequency meet the local
specifications.
No utility
1. Grid is not connected.
2. Check grid connection cables.
3. Check grid usability.
4. If grid is ok and the problem exists still, maybe the fuse in the
inverter is open, please call service.
Low Temp
Over Temp
1. The internal temperature of inverter is higher or lower than
specified normal value.
2. Find a way to reduce or increase the ambient temperature.
3. if the problem remains, please call local service
PV over Voltage:
PV1OVFault
PV2OVFault
1. Check the open PV DC voltage, and see if it is greater than
or too close to 550VDC
2. If PV DC voltage is less than 550VDC, and the problem still
occurs, please call local service.
Permanent Fault
Consistent Faults:
Consist VGrid
Consist Freq
Consist GFCI
Consist DCI
1. Disconnect all PV (+) or PV (-) from solar panels
2. Wait for a few seconds.
3. After the LCD switches off, reconnect and check again.
4. If the problem remains, please call local service.
RelayFail
EEPROM R/W Fail
Sci Comm lose
Spi Comm lose
BusHFault
GFCIDeviceFault
IGridDevice
PLLFault
AutoTestFail
PV Config fault
Fan error
DCI out range
OCPV1
OCPV2
OCIGrid
Summary of Contents for NAC4K-DS
Page 1: ...0...
Page 21: ...20 P N 422 00022 02...