123
Endura
®
Delta
en
User
actual ventilation level according to the programming control is maintained. Therefore, the
ventilation level is not adjusted.
− The Breeze function can also be manually activated using the timer, but the Bypass cannot be.
The Breeze function is automatically activated if the following conditions are fulfilled:
− For 6 hours out of the past 24 hours, it has been warmer than the Breeze temperature
(programmable; is set to 18°C by default; this is the outdoor temperature).
− It is cooler outside than inside.
Tap
■
to enable the automatic Breeze function.
The parameter settings appear. You can then set the Breeze temperature
and the Breeze level.
To exit the menu, briefly tap
▲
and
▼
simultaneously.
Select “Temperature” using
■
and change the temperature using
▲
and
▼
. Confirm your choice by tapping
■
.
The Breeze temperature is equal to the outdoor temperature. The
Breeze function will only be activated when it is cooler outside than
the set outdoor temperature and it has been warmer than the Breeze
temperature for 6 hours out of the past 24 hours.
Select “Breeze level” using
■
and change the level using
▲
and
▼
.
Confirm your choice by tapping
■
.
Once the conditions for the “Breeze” are fulfilled, then this selected level
will be activated.