35
Endura
®
Delta
en
Installer
You can link the air quality sensors to the Master TouchDisplay. These sensors communicate
wirelessly with the Master TouchDisplay. The sensors register the air quality of the room in which
they have been placed and send the flow rate to the Endura Delta. See the diagram below.
See Section 8.2.1.2 on how to link the air quality sensors to the Master TouchDisplay.
50Hz
230V AC ±10%
Netvoeding
Zekeringskast
L PE N
L N
Bijgeleverde
voedingskabel
type JT003-ST3
met IEC-connector
aansluiting via
IEC-connector
bovenaan het toestel
50Hz
230V AC ±10%
Netvoeding
Min. 2 x 0,75 mm
2
I
max
= 1 A
AC
Zekeringskast
Data + power kabel
2 x 0.34mm
2
(data)
2 x 1.00mm
2
(power)
impedantie data 120 Ω
24V
0V
RX IN
TX OUT
24V
0V
TX OUT
RX IN
RX IN
TX OUT
RX IN
TX OUT
24V
0V
TX OUT
RX IN
Data + power cable
2 x 0.34 mm² (data)
2 x 1.00 mm² (power)
impedance data 120 Ω
Power cable type
JT003-ST3(included)
with IEC connector
connected via IEC
connector at the top
of the unit
Min. 2 x 0.75 mm²
I
max
= 1 AAC
Mains supply
Fuse box
Fuse box
Mains supply