60
Endura
®
Delta
en
Installer
Flow Rate Settings
You can change the ventilation levels using this menu. You can define the nominal ventilation level
(design position = C-mode) up to four ventilation levels.
Select “Flow Rate Settings” using
▲
and
▼
, and confirm by tapping
■
.
You can then set the nominal ventilation flow rates. This is equal to the
design flow rate for the entire home. The Endura Delta is a balanced
system, therefore: supply flow rate = extraction flow rate = nominal flow
rate.
You can set the intensity of the four ventilation levels yourself.
L1 = 10% - 50%
Default L1 = 25%
L2 = 10% - 75%
L2 = 50%
L3 = 10% - 100%
L3 = 75%
L4 = 10% - 120%
L4 = 100%
E.g. the total required flow rate for the home is 350 m³/h
Level 1 = 15% of Qnom = 52.5 m³
Level 2 = 40% of Qnom = 140 m³/h
Level 3 = 100% of Qnom = 350 m³/h
Level 4 = 120% of Qnom = boost = 420 m³/h
In this example, Level 3 is equal to the design position. In order to calibrate the unit and measure
the flow rate, you can put the unit into C-mode (see 11.1.3.4.1.9).
Use
▲
and
▼
to select the component to be changed in order to set the
flow rates and levels, and confirm by tapping
■
.
To return to the Installer menu, briefly tap
▲
and
▼
simultaneously.