Bypass Temperature
You can change the Bypass temperature using this menu. This is set to 23°C (indoor temperature)
by default. The Bypass is activated when the following conditions have been met:
− Outdoor temperature > set Bypass temperature - 6°C
− Outdoor temperature < actual indoor temperature
− Indoor temperature > set Bypass temperature (23°C)
Select “Bypass Temperature” using
▲
and
▼
, and confirm by
tapping
■
.
Change the temperature using
▲
and
▼
, and confirm by tapping
■
.
To exit the menu, briefly tap
▲
and
▼
simultaneously.
Electric Preheater (optional)
You can turn the electric preheater on or off using this menu. Please note that not all Endura Delta
units are equipped with a preheater as standard. If you want this element, you must order the
correct type of unit.
If you have an Endura Delta with a preheater, then the “electric preheater” is enabled by default.
Turning off the preheater can accelerate the freezing of the heat exchanger when the conditions
are right for frost to form. We recommend that you do not turn off this function.
Select “Electric Preheater” using
▲
and
▼
, and confirm by tapping
■
.