82
Endura
®
Delta
en
Installer
Err
or
no.
Shor
t
description
System action
Long description
Action
39
Supply pressure sensor value too low
Critical war
ning
The unit has stopped working.
Supply pressure sensor failure. Abnor
mally low value detected via the
pressure sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.
40
Supply pressure sensor value too high
Critical war
ning
The unit has stopped working.
Supply pressure sensor failure. Abnor
mally high value detected via the
pressure sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.
41
Supply pressure sensor static value
Critical war
ning
The unit has stopped working.
Supply pressure sensor failure. The pressure values have remained constant for the past 24 hours.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.
42
Exhaust pressure sensor read error
Critical war
ning
The unit has stopped working.
The exhaust pressure sensor cannot be read.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.
43
Exhaust pressure sensor value too low
Critical war
ning
The unit has stopped working.
Exhaust pressure sensor failure. Abnor
mally low value detected via the
pressure sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.
44
Exhaust pressure sensor value too high
Critical war
ning
The unit has stopped working.
Exhaust pressure sensor failure. Abnor
mally high value detected via the
pressure sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, check the pressure lines and pressure openings. Check to see if there are any obstructions or build-up present.
3.
If there are no obstructions or build-up present, then the motherboard may need to be replaced.