8 4
Endura
®
Delta
en
Installer
Err
or
no.
Shor
t
description
System action
Long description
Action
51
Extract air CO
2
sensor missing
W
ar
ning
The unit continues to operate.
The CO
2
sensor cannot be found during
star
t-up, although this was found during
previous activations of the unit. This means that the sensor has been damaged or has come loose.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, tr
y reconnecting the connectors or
replace the CO
2
printed circuit board.
52
Extract air CO
2
read error
W
ar
ning
The unit continues to operate.
An error occurred when reading the CO
2
sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, tr
y reconnecting the connectors or
replace the CO
2
printed circuit board.
3.
If the error message remains, then the motherboard may need to be replaced.
53
Extract air CO
2
too low
Critical war
ning
The unit has stopped working.
Abnor
mally low CO
2
value detected via
the CO
2
sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, tr
y reconnecting the connectors or
replace the CO
2
printed circuit board.
3.
If the error message remains, then the motherboard may need to be replaced.
54
Extract air CO
2
too high
Critical war
ning
The unit has stopped working.
Abnor
mally high CO
2
value detected via
the CO
2
sensor
.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, tr
y reconnecting the connectors or
replace the CO
2
printed circuit board.
55
Extract air CO
2
static
Critical war
ning
The unit has stopped working.
CO
2
sensor failure. The CO
2
values have
remained constant for the past 24 hours.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If the error message remains, tr
y reconnecting the connectors or
replace the CO
2
printed circuit board.
3.
If the error message remains, then the motherboard may need to be replaced.
56
Invalid error
Critical war
ning
The unit has stopped working.
An invalid error has occurred.
1.
Tur
n off the power for 30 seconds and then restar
t the unit.
2.
If this error reappears after restar
ting the unit, please contact your
installer/the Renson after
-sales ser
vice.