6.2.4 • Guidelines for the supply air and extract air
• The supply and discharge of outdoor/indoor air must be positioned in such a way that it is
impossible to recirculate “polluted” air. Therefore, sufficient distance between the outdoor
air supply opening and the sewer ventilation, indoor air discharge opening, extractor for the
combustion gasses, etc. must be maintained.
According to the
Ventilation technical information (TI)
- practical guidelines, the following
recommendations will restrict the risk of recirculation:
• Respect a difference in height of at least 2 m between the supply and discharge. The supply
must always be lower than the discharge. If this difference in height is not possible, then there
must be a minimum of 10 m between the supply and discharge.