6.2.5 • Connecting the condensate discharge
Condensate
discharge unit
Screw connection
Rubber ring
Condensate
discharge pipe
Schroefverbinding
Rubberring
Condensafvoerbuis
Condensafvoer toestel
• The ventilation unit is always supplied with a condensate
discharge Ø32 mm (external diameter)
• A connective duct is also supplied in a recess in the EPS block
on which the unit is supplied.
• Place the rubber ring at the
top of this pipe and screw
it tight to the condensate
discharge on the unit.
• The condensate discharge
must be connected to the
internal sewerage using a
permanent pipe or hose via
a water seal (siphon).
! The water seal must be filled with water when it is installed (keeping residual odours to a
minimum).
! The end of the pipe or hose must discharge under the water low enough (min.
60 mm) to prevent the unit from taking in air leaked via the condensate discharge.
Schroefverbinding
Rubberring
Condensafvoerbuis
Condensafvoer toestel