Battery Status Menu
6
.
V Output Power Menu
7
.
Temperature Menu
8
.
History Record Menu
19
9
.
Bypass Range Set Menu
A. To protect the load, the function of
bypass auto-transfer is activated
only when the AC main voltage is
within the range of LO (low) and
HI(high). In this screen, press on/off
Control Key to enter the following
steps for LO/HI voltage setting..
B. The cursor (
→
) will pop up to
indicate the item newly selected.
Press on/off Control Key to get the
item of LO or HI range the user
want to adjust.
C. Use Up or Down-key to adjust the
voltage (changing 1V by every
press). LO (low rang):176V+/- 20V,
HI(high range):253V+/- 20V).
D. Once the value is confirmed, press
on/off Control Key again to save the
data.