4.  INSTALLATION 

   Installation and wiring must be performed in accordance with the local 

    electric code and the following instructions by professional personnel. 

   For safety, please cut off the mains power switch before installation.     

   The battery breaker also needs to be cut off. 

 

1. 

Open the terminal block cover located on the rear panel of the 

       UPS

please refer to the appearance diagram. 

2. 

For 6K UPS, it is recommended to select the UL1015 10AWG 

   

6mm2

wire or other insulated wire which complies with AWG   

    Standard for the UPS input and output wirings. 

3. 

For 10K UPS, it is recommended to select the UL1015 8AWG 

(10mm2

wire or other insulated wire which complies with AWG 

  Standard for the UPS input and output wirings.     

4. 

To connect the load with the UPS, please turn off all the loads first,   

     then perform the connection and finally turn on the loads one by one. 

5. 

Connect the input and output wires to the corresponding input and 

  output terminals according to the following diagram 

  Note: you must make sure that the input and output wires and   

        the input and output terminals are connected tightly. 

6. 

After having completed the installation, make sure the wiring is   

     correct. 

7. 

If the UPS connect external batteries, make sure the battery polarity 

  and voltage are correct. 

 

Note:  Do  not use the  wall  receptacle  as the input power source for 

the UPS, as its rated current is less than the UPS’s maximum input 

current. Otherwise the receptacle may be burned and destroyed. 

 

Summary of Contents for RP-UPH103T

Page 1: ...User manual RP UPH 6K 10K ON LINE UPS REV 2...

Page 2: ...Contents 1 Introduction 1 2 Safety Instructions 2 3 System Description 4 4 Installation 8 5 Operation 9 6 Trouble Shooting Guide 14 7 Communication 15 8 Specification 16...

Page 3: ...start function 3 LED and LCD display for detail status and data real time alarm silence 4 Remote monitoring with SNMP intelligent slot and RS 232 interface 5 Light weight and compact size easy to tra...

Page 4: ...S on rugged or declined surface 2 Do not install the UPS system near water or in damp environments 3 Do not install the UPS system where it would be exposed to direct sunlight or near heat 4 Do not bl...

Page 5: ...supervise operations Unauthorized persons must be kept well away from the batteries 3 Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures s...

Page 6: ...battery voltage battery capacity left output load and inside temperature UPS output voltage frequency can be set from it here too 2 Up key Press Up key to select upward Switch Off press both Up key 2...

Page 7: ...ine mode press and hold both Up key 2 and Enter key 4 simultaneously for 3 seconds to initiate the self test 10 seconds 5 Fault LED red To indicate the UPS has an internal fault 6 Warning LED yellow T...

Page 8: ...6 3 2 OUTLINE 6K 10K Tower...

Page 9: ...port 3 EPO connector 4 Parallel connection 5 Intelligent slot 6 Fan 7 External battery connector 8 Input breaker 9 Input Output terminal 10 Classic ground screw 11 Maintain bypass switch 12 IEC Circui...

Page 10: ...insulated wire which complies with AWG Standard for the UPS input and output wirings 4 To connect the load with the UPS please turn off all the loads first then perform the connection and finally tur...

Page 11: ...ready to switch on the inverter 2 By pressing the Enter key and the Down key simultaneously for 3 seconds the UPS will start up after two beeps and Normal LED lights up to indicate the power is from i...

Page 12: ...10 5 4 LCD display Use Up Down key to select menu displays of the LCD described below This screen will refresh once the system power is enabled 1 Rated specification 2 Status 3 Voltage 4 Frequency...

Page 13: ...11 5 Battery status 6 Output power 7 Temperature...

Page 14: ...ng range the bypass output will be closed automatically to protect the load In this screen press Enter key to enter the following steps for LO HI voltage setting B The cursor will pop up to indicate t...

Page 15: ...ltage and frequency Press Enter key to confirm voltage and then the cursor will move to frequency selection The output voltage 208V 220V 230V or 240V are available The output frequency 50Hz 60Hz 50HzP...

Page 16: ...ase contact your agent for service 3 AC utility power is normal but UPS is overloaded Warning LED lits up and buzzer beeps But UPS has not switched to bypass Please reduce the critical load to 100 4 A...

Page 17: ...S400 card to achieve remote management of the UPS Please contact your local distributor for further information 2 The following are the descriptions and pin assignment of RS232 DB 9 port Baud rate 240...

Page 18: ...Hz 60Hz 0 1Hz Outlet Terminal blocks IEC outlet 2 Wave form True sine wave Frequency lock range 50Hz 60Hz 4Hz Overload Line mode 100 110 10minutes 110 130 1 minute 130 1 second Overload Battery mode 1...

Reviews: