9. Output voltage/frequency setting
(Under AC mode, this menu is displayed before turning the UPS on)
A. In this screen, press Enter-key
to
enter the following steps for output
voltage and frequency setting.
B. The cursor (
→
) will pop up to indicate
the output voltage and frequency
newly selected.
C. Use Up
or Down-key
to adjust
the output voltage and frequency.
Press Enter-key
to confirm voltage
and then the cursor will move to
frequency selection.
The output voltage ( 208V, 220V, 230V
or 240V) are available.
The output frequency ( 50Hz, 60Hz,
50HzP or 60HzP ) are available.
UPS is off without
bypass output once
the frequency (50Hz or 60Hz) is selected.
UPS is off with
bypass output once the
frequency (50HzP or 60HzP) is selected.
D. Once the correct voltage(or frequency) is
selected, press Enter-key
again to save
the selection.
The new setting will be performed after
The UPS is restarted.