4.
Connection and Installation
The system may be installed and wired only by qualified electricians in
accordance with applicable safety regulations!
4.1 Unpacking and Inspection for 6K(L)/10K(L)
1. Unpack the packaging and check the package contents. The
shipping package contains:
A UPS
A user manual
A communication cable
A battery cable (for AHA-603HL/104HL only)
2. Inspect the appearance of the UPS to see if there is any damage
during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.
4.2 Input and output power cords and protective earth ground installation
1. Notes for installation
(a) The UPS must be installed in a location with good ventilation, far
away from water, inflammable gas and corrosive agents.
(b) Ensure the air vents on the front and rear of the UPS are not
blocked. Allow at least 0.5m of space on each side.
(c) Condensation to water drops may occur if the UPS is unpacked
in a very low temperature environment. In this case it is
necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of
electric shock.
9