(c) Connect the output wires of each UPS to an output breaker
panel.
(d) Disconnect the Jumper on JP1 and JP2 of the terminal block
first, and connect each output breaker to a main output breaker
and then to the loads.
*
The requirement of the output wiring is as follows:
When the distance between the UPSs in parallel and the
breaker panel is less than 20 meters, the difference
between the wires of input & output of the UPSs is
required to be less than 20%.
When the distance between the UPSs in parallel and the
breaker panel is greater than 20 meters, the difference
between the wires of input & output of the UPSs is
required to be less than 10%.
15