(h) Take apart the board of parallel ports when UPS has turned to
bypass mode, insert the other end of combine line into parallel
card’s slot and screw down its pin; and then lock up the board of
parallel ports over again
(i) Close line input switch of all UPS (including new UPS) in the
parallel system; lock up maintain board, unless all UPS turn to
bypass mode; press the open key in turn, observe whether the
display state of every UPS is normal; at the same time, observe
whether all UPS all together turn to inverter model; and measure
the voltage difference of every UPS ports’ JP2.
(j) Turn off all UPS, take apart maintain board of all UPS unless they
all have turned to bypass mode. Turn all the maintain switches
from “BPS” to “UPS” and lock up every maintain board.
(k) Turn on UPS, make all UPS changed into line inverter mode to
work parallel.
Note: If the state of UPS is abnormal in step 8, please
follow operational process of removing single UPS to
maintain.
2. Process of removing single UPS
(a) If want to remove UPS which is running normally, please
press the close key of the removing one continuously for 2
times
(b) Shut off the UPSs own line switch, line output switch outside
and battery switch, when this UPS need to remove out.
23
Summary of Contents for RP-UPH104T
Page 1: ...USER S MANUAL On Line 6K 10KVA Uninterruptible Power Supply...
Page 19: ...Battery Status Output Power Temperature History Record 18...
Page 36: ...DB 9 Interface of AS400 communication protocol 35...
Page 39: ...Appendix 1 Outline Description and Back Panel Back view of 6K Back view of 6KL 38...
Page 40: ...Back view of 10K Back view of 10KL 39...
Page 41: ...40...