(c) Turn off other UPS which are running, take apart the
maintain cover of every UPS and turn all UPS maintain
switch from “UPS” to “BPS” until all running UPS turn to BPS
mode. Then turn off every UPS own input switch.
(d) After removing single UPS, if leaving UPS system is
changed to single running, please connect the short line
between JP1 and JP2 of this UPS output port.
(e) Take apart another UPS parallel cover and combine line
connected with the UPS which need to remove until all UPS
panels become black, then lock up the cover of parallel ports
again.
(f) Take apart UPS parallel cover and combine line when the
UPS have to remove, then lock up the cover of parallel ports
again.
(g) Shut input line switch of leaving UPS system, turn maintain
switch from “BPS” to “UPS” until all UPS turn to BPS mode
and lock up the maintain cover, then turn on the machine and
turn all UPS to line inverter mode running.
3. Combine machine warning
(a) When UPS combine system work at inverter mode, make
sure that all UPS maintain switches at the same place, that is
to say, be at the position of “UPS”, or be at the position of
“BPS”.
(b) When turning on the UPS combine system before enter into
inverter mode, UPS output switch must at “OFF” model.
(c)
When UPS combine system work at inverter model, please
do not operate any UPS maintain switch.
24
Summary of Contents for RP-UPH104T
Page 1: ...USER S MANUAL On Line 6K 10KVA Uninterruptible Power Supply...
Page 19: ...Battery Status Output Power Temperature History Record 18...
Page 36: ...DB 9 Interface of AS400 communication protocol 35...
Page 39: ...Appendix 1 Outline Description and Back Panel Back view of 6K Back view of 6KL 38...
Page 40: ...Back view of 10K Back view of 10KL 39...
Page 41: ...40...