background image

INSTALLATION INSTRUCTIONS

69-0317-05

393200-1 ECO Connector for the 
VR8200 Family of Continuous Pilot 
Combination Gas Controls

APPLICATION

The393200-1 ECO Connector ls an optional device for 

V8200 and VR8200 continuous pilot combination gas 

controls that allows connecting a high-limit ECO into the 

thermocouple circuit. It can be used only with the V8200 

and VR8200 models.

With an ECO switch in the thermocouple circuit, safety 

shutoff can be initiated on high-limit action. The ECO 

switch senses plenum temperature and breaks the 

thermocouple circuit if plenum temperature rises too 

high. 

Leadwires from the high limit or ECO must be equipped 

with insulated 1/4-in. female quick-connect terminals. 

Leadwire lengths must not exceed the lengths shown in 

Table 1 and 2.

Table 1. Maximum Length of Supplementary Limit Leadwires when Using Q340A Thermocouple

Thermocouple 

Length

Maximum Leadwire Length x 2 (wires)

AWG NO. 14 

AWG NO. 16

AWG NO. 18

in.

m

in.

m

in.

m

in.

m

12

0.3

41

1.0

26

0.7

16

0.4

18

0.5

35

0.9

22

0.6

13

0.3

24

0.6

29

0.8

18

0.5

11

0.3

30

0.8

23

0.6

15

0.4

9

0.2

36

0.9

17

0.4

11

0.3

6

0.2

40

1.0

13.

0.3

8

0.2

48

1.2

Do Not Use

54

1.4

60

1.5

72

1.8

Table 2. Maximum Length of Supplementary Limit Leadwires when Using Q309A Thermocouple

Thermocouple 

Length

Maximum Leadwire Length x 2 (wires)

AWG NO. 14 

AWG NO. 16

AWG NO. 18

in.

m

in.

m

in.

m

in.

m

12

0.3

47

1.2

30

0.8

18

0.5

18

0.5

41

1.0

26

0.7

16

0.4

24

0.6

35

0.9

22

0.6

14

0.4

30

0.8

29

0.8

18

0.5

11

0.3

36

0.9

23

0.6

15

0.4

9

0.2

40

1.0

19

0.5

12

0.3

7

0.2

48

1.2

11

0.3

7

0.2

54

1.4

Do Not Use

60

1.5

72

1.8

Reviews: