MU1H-1181GE23 R0
520
4
GB
9.3. Adjusting the setting scale
If the adjustment knob is removed, this setting is lost. A new
setting can be achieved using a pressure gauge.
1. Close shutoff valve on inlet
2. Close shutoff valve on outlet
3. Release pressure on outlet side (e.g. through water tap)
4. Loosen slotted screw
• Do not remove slotted screw
5. Slowly open shutoff valve on inlet
6. Set desired outlet pressure (e.g. 4 bar)
7. Align scale (e.g. 4) in middle of viewing window
8. Retighten slotted screw
9. Slowly open shutoff valve on outlet
9.4. Cleaning
If necessary, the filter bowl and the filter can be cleaned.
1. Close shutoff valve on inlet
2. Close shutoff valve on outlet
3. Release pressure on outlet side (e.g. through water tap)
4. Unscrew filter bowl
• Use double ring wrench ZR06K
5. Remove filter cartridge
6. Remove filter insert
7. Clean sieve
8. Clean filter bowl
9. Mount the filter insert
10. Re-insert the filter insert
11. Put O-ring on filter bowl
12. Screw filter bowl in place
13. Slowly open shutoff valve on inlet
14. Slowly open shutoff valve on outlet
10. Disposal
• Dezincification resistant brass housing
• Brass threaded connections
• High-quality synthetic material valve insert
• High-quality synthetic material spring bonnet with adjust-
ment knob and setting scale
• Spring steel adjustment spring
• Stainless steel fine filter
• Red-bronze or shock-resistant, clear transparent synthetic
material filter bowl
• Fibre-reinforced NBR diaphragm
• Seals
• Brass hose nozzle
Caution !
Do not use any cleaning agents containing solvents
and/or alcohol to clean the plastic parts!
Frequency: at least every 2 month (depending on local
operating conditions
• Non-compliance can lead to the filter becoming
blocked This results in a drop in pressure and
decreased water flow
• The filter meshes are made of stainless steel. A red
coating as a consequence of rust from the pipelines
has no influence on function or the way the filter
works
To be carried out by an installation company or the
operator.
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
Observe the local requirements regarding correct waste
recycling/disposal!
11. Troubleshooting
Problem
Cause
Remedy
Beating sounds
Filter combination is too large
Call our Technical Customer Services
Water is escaping from the spring
bonnet
Diaphragm in valve insert is faulty
Replace valve insert
Too little or no water pressure
Shutoff valves upstream or downstream
from filter not fully open
Open the shutoff valves fully
Filter combination is not set to the
desired outlet pressure
Set outlet pressure
Filter mesh dirty
Clean or replace filter
Not fitted in flow direction
Fit filter in flow direction (note direction of arrow
on housing)
The outlet pressure set does not
remain constant
Filter mesh dirty
Clean or replace filter
Valve insert, sealing ring or edge of
nozzle is contaminated or worn
Replace valve insert
Rising pressure on outlet (e.g. in boiler) Check check valve, safety group etc.