GB
2
MU1H-1126GE23 R0220
1
Safety Guidelines
1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2
Technical Data
Note:
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be
proven individually.
3
Options
For Options visit homecomfort.resideo.com/europe
4
Assembly
4.1 Installation Guidelines
•
Install in horizontal pipework with filter bowl
downwards
– This position ensures optimum filter efficiency
•
Install shut-off valves
•
These filters are armatures which need to be
maintained regularly
•
Ensure good access
– Degree of contamination can be easily seen with
clear filter bowl
– Simplifies maintenance and inspection
•
The installation location should be protected against
frost
•
Related to the EN 806-2 it is recommended to install
the filter immediately after the water meter
•
In order to avoid flooding, it is recommended to
arrange a permanent, professionally dimensioned
wastewater connection
4.2 Assembly instructions
We recommend to install an inlet check valve
CAUTION!
Observe the flow direction when mounting the
backflow preventer.
CAUTION!
When using soldering connections, do not solder
the connections together with the filter combination.
High temperature will irreparably damage important
internal working components!
1.
Thoroughly flush pipework
2.
Fit filter combination
• Note flow direction
• Install without tension or bending stresses
3.
Seal in pressure gauges
4.
Set outlet pressure
4.3 Drain for rinse water
The rinse water must be piped to the drain in such a
way that no back pressure can occur
1.
Discharge into drain connector
2.
Discharge into floor drain
*at 4 bar inlet pressure and a rinse duration of 15 seconds
5
Start-up
5.1 Setting outlet pressure
Set outlet pressure min. 1 bar under inlet pressure.
1.
Close shut-off valve on inlet
2.
Release pressure on outlet side (e.g. through water
tap)
3.
Close shut-off valve on outlet
Media
Medium: Drinking
water
Connections/Sizes
Connection sizes:
1
/
2
" - 1
1
/
4
"
Pressure values
Max. operating pressure:
16 bar
Inlet pressure:
max. 16 bar
Outlet pressure:
1.5 - 6 bar
Operating temperatures
Max. operating temperature
medium accord. to EN 1567
(Plastic filter bowl):
30 °C AA
Max. operating temperature
medium (10 bar/Metal filter
bowl):
70 °C AAM
Specifications
Installation position:
Horizontal with filter bowl
downwards
Filter size
Reverse rinsing
quantity*
C (mm)
3
/
4
" - 1
1
/
4
“ 25
litres
20