V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS

69-0329—05

2

WARNING

Fire or Explosion Hazard

Can cause property damage, severe injury, or 

death.

Follow these warnings exactly:

1. Disconnect power supply before wiring to 

prevent electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas, 

turn off gas supply at the appliance service 

valve before starting installation, and perform 

Gas Leak Test after completion of installation.

3. Always install sediment trap in gas supply line 

to prevent contamination of gas control.

4. Do not force the gas control knob. Use only 

your hand to turn the gas control knob. Never 

use any tools. If the gas control knob will not 

operate by hand, call a qualified service 

technician to replace the gas control. Force or 

attempted repair can result in fire or explosion.

CAUTION

Never apply a jumper across or short the valve 

coil terminals. This can burn out the heat 

anticipator in the thermostat or damage the 

electronic direct ignition (DI) module.

IMPORTANT:

These gas controls are shipped with protective 

seals over inlet and outlet tappings. Do not 

remove seals until ready to connect piping.

Follow the appliance manufacturer instructions if 

available; otherwise, use the instructions provided below.

Converting Between Natural and LP Gas

WARNING

Fire or Explosion Hazard

Can cause property damage, severe injury, or 

death.

1. Do not use a gas control set for natural gas on 

an LP gas system or a gas control set for LP 

gas on a natural gas system.

2. When making conversion, main pilot burner 

orifices must be changed to meet appliance 

manufacturer specifications.

Refer to appliance manufacturer instructions for orifice 

specifications and changeover procedure. Gas controls 

are factory-set for natural (and manufactured) or LP gas. 

Do not attempt to use a control set for natural 

(manufactured) gas on LP gas, or a control set for LP on 

natural (manufactured) gas.

Gas controls with standard or slow opening regulators 

can be converted from one gas to the other with a 

conversion kit (ordered separately). Order part no. 

393691 to convert from natural (manufactured) to LP 

gas; order part no. 394588 to convert from LP to natural 

(manufactured) gas. Controls with step opening 

regulators cannot be converted.

Install Adapters to Control

If adapters are to be installed on the gas control, mount 

them as follows:

Flanges

1.

Choose the appropriate flange for your application.

2.

Remove seal over gas control inlet or outlet.

3.

Make sure the O-ring fits into the flange groove. If 

the O-ring is not attached or is missing, do not use 

the flange.

4.

With the O-ring facing the gas control, align the 

screw holes on the gas control with the holes in the 

flange. Insert and tighten the screws provided with 

the flange. See Fig. 1. Tighten the screws to 25 

inch-pounds of torque to provide a gas-tight seal.

Fig. 1. Fasten flange to valve firmly, but do not 

overtighten screws.

Bushings

1.

Remove seal over gas control inlet or outlet.

2.

Apply moderate amount of good quality pipe com-

pound to bushing, leaving two end threads bare. On 

LP installation, use compound resistant to LP gas. 

Do not use Teflon tape.

3.

Insert bushing in control and carefully thread pipe 

into bushing until tight.

Complete instructions below for piping, installing con-

trol, and wiring. Make certain the leak test you perform 

on the control after completing the installation includes 

leak testing the adapters and screws. If you use a wrench 

on the valve after flanges are installed, use the wrench 

only on the flange, not the control. Refer to Fig. 5. Insert 

bushing in gas control and carefully thread pipe into the 

bushing until tight.

Location

The combination gas control is mounted in the appliance 

vestibule on the gas manifold. If this is a replacement 

application, mount the gas control in the same location 

as the old control.

Locate the combination gas control where it cannot be 

affected by steam cleaning, high humidity, or dripping 

water, corrosive chemicals, dust or grease accumulation 

or excessive heat. To assure proper operation, follow 

these guidelines:

To safeguard proper operation, follow these guidelines:

• Locate gas control in a well-ventilated area. Mount 

gas control high enough above the cabinet bottom to 

avoid exposure to flooding or splashing water.

• Assure the ambient temperature does not exceed the 

ambient temperature ratings for each component.

M9046

VALVE OUTLET

FLANGE

9/64 INCH HEX SCREWS (4) 

DO NOT OVERTIGHTEN SCREWS.  TIGHTEN TO 

25 INCH-POUNDS.

1

1

Summary of Contents for V8205

Page 1: ...s noted Approvals American Gas Association design certificate L2025006 Canadian Gas Association design certificate L2025006 Australian Gas Association design certificate 4214 Approved for Delta C applications INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a haz ardous condition 2 Check the ratings given in the ...

Page 2: ...t no 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted Install Adapters to Control If adapters are to be installed on the gas control mount them as follows Flanges 1 Choose the appropriate flange for your application 2 Remove seal over gas control inlet or outlet 3 Make sure the O ring fits into the flange groove If the O ring is not at...

Page 3: ...erted too deeply refer to Table 4 4 Apply a moderate amount of good quality pipe com pound do not use Teflon tape to pipe only leaving two end threads bare On LP installations use compound resistant to LP gas See Fig 3 5 Remove seals over control inlet and outlet if neces sary 6 Connect pipe to control inlet and outlet Use wrench on the square ends of the control If a flange is used place wrench o...

Page 4: ...d other con trols as required 2 Connect control circuit to gas control terminals See Fig 4 6 and 7 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve operator NOTE Use leadwires with insulated terminals Fig 6 Wiring connections for 24 volt control in S87 direct ignition system APPLY WRENCH FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WREN...

Page 5: ...n the appliance nameplate or manufacturer recommended burner orifice pressure for the size orifice s used Make certain the primary air supply to the main burner is properly adjusted for complete combustion refer to the appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Make certain there is no gas flow through the meter other than to the appliance being checked O...

Page 6: ...ure to the control 5 STEP OPENING PRESSURE REGULATORS ONLY Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at least 30 seconds between cycles for regulator to resume step function Repeat after allowing burner to cool Readjust full rate outlet pressure if necessary t...

Page 7: ... manual valve in the gas piping to the appliance or on LP at the tank Do not try to light any appliance Do not touch any electrical switch or use the phone Leave the building and call your gas supplier If your gas supplier cannot be reached call the fire department 2 Do not force the gas control knob on the appli ance Use only your hand to turn the gas con trol knob Never use any tools If the knob...

Page 8: ...5422 1 800 468 1502 69 0329 05 M S Rev 09 20 Printed in United States 6 If you don t smell gas turn knob on gas control counterclockwise to ON 7 Replace the burner access panel 8 Reset the thermostat to the desired temperature 9 If the burner does not come on when the room temperature is below thermostat setting turn gas control knob to OFF and contact a qualified ser vice technician for assistanc...

Reviews: