background image

V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS

69-0329—05

4

Fig. 5. Proper use of wrench on gas control with and without flanges.

WIRING

Follow the wiring instructions furnished by the appliance 

manufacturer, if available, or use the general instructions 

provided below. Where these instructions differ from the 

appliance manufacturer, follow the appliance 

manufacturer’s instructions.

All wiring must comply with applicable electrical codes 

and ordinances.

Disconnect power supply before making wiring 

connections to prevent electrical shock or equipment 

damage.

1.

Check the power supply rating on the gas control 

and make sure it matches the available supply. 

Install the trans-former, thermostat, and other con-

trols as required.

2.

Connect control circuit to gas control terminals. 

See Fig. 4, 6, and 7.

3.

Adjust thermostat heat anticipator to 0.50A rating 

stamped on valve operator.

NOTE:

Use leadwires with insulated terminals.

Fig. 6. Wiring connections for 24 volt control in S87 

direct ignition system.

APPLY WRENCH 
FROM TOP OR 
BOTTOM OF GAS 
CONTROL TO 
EITHER SHADED AREA

WHEN FLANGE IS NOT USED

APPLY WRENCH
TO FLANGE ONLY

WHEN FLANGE IS USED

M3084A

24V

24V (GND)

S87B CONTROL MODULE

ALARM

VALVE

VALVE

GND

TEMPERATURE 

CONTROLLER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM IGNITER-SENSOR CABLE LENGTH:  3 ft. (0.9 m) OR LESS.

3A REPLACEABLE FUSE.

ALARM TERMINAL PROVIDED ON SOME MODELS.

M9043A

MV

MV

L1

(HOT)

L2

1

2

1

2

3

DUAL VALVE

COMBINATION

GAS CONTROL

Q347 IGNITER-SENSOR

BURNER

4

4

5

IGNITER-SENSOR AND 

BURNER GROUND

3

5

ALARM, IF USED

Summary of Contents for V8205

Page 1: ...s noted Approvals American Gas Association design certificate L2025006 Canadian Gas Association design certificate L2025006 Australian Gas Association design certificate 4214 Approved for Delta C applications INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a haz ardous condition 2 Check the ratings given in the ...

Page 2: ...t no 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted Install Adapters to Control If adapters are to be installed on the gas control mount them as follows Flanges 1 Choose the appropriate flange for your application 2 Remove seal over gas control inlet or outlet 3 Make sure the O ring fits into the flange groove If the O ring is not at...

Page 3: ...erted too deeply refer to Table 4 4 Apply a moderate amount of good quality pipe com pound do not use Teflon tape to pipe only leaving two end threads bare On LP installations use compound resistant to LP gas See Fig 3 5 Remove seals over control inlet and outlet if neces sary 6 Connect pipe to control inlet and outlet Use wrench on the square ends of the control If a flange is used place wrench o...

Page 4: ...d other con trols as required 2 Connect control circuit to gas control terminals See Fig 4 6 and 7 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve operator NOTE Use leadwires with insulated terminals Fig 6 Wiring connections for 24 volt control in S87 direct ignition system APPLY WRENCH FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WREN...

Page 5: ...n the appliance nameplate or manufacturer recommended burner orifice pressure for the size orifice s used Make certain the primary air supply to the main burner is properly adjusted for complete combustion refer to the appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Make certain there is no gas flow through the meter other than to the appliance being checked O...

Page 6: ...ure to the control 5 STEP OPENING PRESSURE REGULATORS ONLY Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at least 30 seconds between cycles for regulator to resume step function Repeat after allowing burner to cool Readjust full rate outlet pressure if necessary t...

Page 7: ... manual valve in the gas piping to the appliance or on LP at the tank Do not try to light any appliance Do not touch any electrical switch or use the phone Leave the building and call your gas supplier If your gas supplier cannot be reached call the fire department 2 Do not force the gas control knob on the appli ance Use only your hand to turn the gas con trol knob Never use any tools If the knob...

Page 8: ...5422 1 800 468 1502 69 0329 05 M S Rev 09 20 Printed in United States 6 If you don t smell gas turn knob on gas control counterclockwise to ON 7 Replace the burner access panel 8 Reset the thermostat to the desired temperature 9 If the burner does not come on when the room temperature is below thermostat setting turn gas control knob to OFF and contact a qualified ser vice technician for assistanc...

Reviews: