3.1.15 Tube collector function
If the controller detects an increase in collector tempera-
ture by 2 K compared to the previously stored collector
temperature, the solar pump will be switched-on for about
30 seconds in order to detect the fluid temperature. After
this, the current collector temperature will be saved as a
new reference value. If the measured temperature (new
reference value) is exceeded by 2 K, the solar pump will
run for 30 seconds. SIf the switch-on difference between the
collector and the store is exceeded during the runtime of
the solar pump or the standstill of the system, the controller
will automatically switch to solar loading.
If the collector temperature deacreases by 2 K during stand-
still, the switch-on value for the tube collector function will
be recalculated.
O TC:
Tube collector function
Adjustment range: OFF ... ON
Factory setting: OFF
For control and service work, the operating mode of the
controller can be manually adjusted. For this purpose, select
the adjustment value HND1. The following adjustments can
be carried out:
3.1.17 Operating mode
OFF : relay off
(flashing) +
AUTO : relay in automatic operation
ON : relay on
(blinkend) +
HND1:
Operating mode
Adjustment range:
OFF, AUTO, ON
Factory setting: AUTO
3.1.18 Language (LANG)
In this channel, different languages are available.
•
dE : German
•
En : English
•
It : Italian
•
Fr : French
LANG:
Language choice
Adjustment range:
dE, En, It, Fr
Factory setting: En
3.1.16 Speed control
A relative minimum pump speed is allocated to the output
R1 via the adjustment channel
nMN
.
ATTENTION:
When loads which are not speed controlled (e.g.
valves) are used, the value must be changed to 100 %
in order to deactivate pump speed control.
nMN:
Pump speed control
Adjustment range: 30 ... 100
Factory setting: 30