If a reference relay has been selected, the fl ow rate monitoring function will become
active when the allocated relay switches on. In case of an error, the complete solar
system will be shut down.
The error message will appear both in the Status / Messages menu and in the
Status / Arrangement / Flow rate mon. menu. It can be acknowledged in the
Status / Arrangement / Flow rate mon. menu only.
10 Heating
In this menu, all adjustments for the heating part of the arrangement or for the
heating circuits respectively can be made.
10.1 Shared relays
In this menu, adjustments for heat generators which are shared by several heating
circuits and their optional functions can be made.
Shared relays will be available for selection under Virtual in the heating circuits
and in the relay allocation channels of the corresponding optional functions of the
heating menu. This way, several heating circuits and optional functions (heating) can
demand the same heat source.
Note
Activate and adjust the shared relays fi rst. They will then be available in
the heating circuits and optional functions.
Heating / Shared rel.
A d j u s t m e n t
channel
Description
Adjustment range / se-
lection
Factory setting
Dem. 1 (2)
Demand 1 (2)
Activated, Deactivated Deactivated
Relay
Relay option
Yes, No
No
Relay
Relay submenu
-
-
Relay
Relay selection
system dependent
system dependent
Boiler pr. min
Option for boiler protection
min
Yes, No
No
TMin
Minimum boiler temperature 10 … 90 °C
55 °C
Boiler pr. max
Option for boiler protection
max
Yes, No
No
TMax
Maximum boiler temperature 20 … 95 °C
90 °C
Sen. boiler
Boiler sensor selection
system dependent
S4
0-10 V
0-10 V option
Yes, No
No
0-10 V
0-10 V submenu
-
-
Output
Output selection
-, A, B, C, D
-
TSet 1
Lower boiler temperature
10 … 85 °C
10 °C
Volt 1
Lower voltage
1.0 … 10.0 V
1.0 V
TSet 2
Upper boiler temperature
15 … 90 °C
80 °C
Volt 2
Upper voltage
1.0 … 10.0 V
8.0 V
Permanent volt. Permanent voltage option
Yes, No
No
Volt
Permanent voltage value
0.1 … 9.9 V
2.0 V
TMin
Minimum value set boiler
temperature
10 … 89 °C
10 °C
TMax
Maximum value set boiler
temperature
11 … 90 °C
80 °C