81
en
Adjustment
channel
Description
Adjustment range / se-
lection
Factory setting
D
TOff
Switch-off temperature difference -14.5 … 45.0 K
15.0 K
Loading
pump
Boiler loading pump output
selection
system dependent
system depend-
ent
Start. opt.
Starting optimisation option
Yes, No
No
Time
Starting optimisation time
0 … 300 min
60 min
Stopp. opt.
Stopping optimisation option
Yes, No
No
Time
Stopping optimisation time
0 … 300 min
60 min
Solar off
Solar off option
Yes, No
No
Store
Allocation solar store
all solar stores
-
Stset
Set temperature option
Yes, No
No
SFB off
Solid fuel boiler off option
Yes, No
No
SFB
Allocation solid fuel boiler
all solid fuel boilers
-
DHW
priority
DHW priority option
Yes, No
No
Chimney
sweeper
Chimney sweeper option
Yes, No
Yes
Antifreeze
Antifreeze option
Yes, No
No
Sensor
Antifreeze sensor
Flow, Outdoor
Flow
TAntifr.
Antifreeze temperature
-20 … +10 °C (Out-
door)
4 … 10 °C (Flow)
+2 °C (Outdoor)
+5 °C (Flow)
TFlowset
Set flow temperature antifreeze
20 … 50 °C
20 °C
Heat dump
Heat dump option
Yes, No
No
Heat dump
Heat dump submenu
-
-
Sensor
Allocation heat dump sensor
system dependent
system depend-
ent
TOn
Switch-on temperature heat dump 25 … 95 °C
85 °C
TOff
Switch-off temperature heat dump 20 … 90 °C
50 °C
TFlowset
Set flow temperature heat dump
5 … 90 °C
50 °C
Cooling
system
Cooling system submenu
-
-
Mode
Cooling mode
Linear, Constant
Constant
TFlow
Cooling flow temperature
5 … 25 °C
20 °C
TFlowmin
Minimum flow temperature
5 … 29 °C
10 °C
TOutdoor 1 Lower outdoor temperature
15 … 45 °C
20 °C
TFlow 1
Lower set flow temperature
5 … 25 °C
20 °C
TOutdoor 2 Upper outdoor temperature
15 … 45 °C
40 °C
TFlow 2
Upper set flow temperature
5 … 25 °C
10 °C
TFlowmin
Minimum flow temperature
5 … 29 °C
10 °C
TFlowmax
Maximum flow temperature
6 … 30 °C
25 °C
Adjustment
channel
Description
Adjustment range / se-
lection
Factory setting
Output
Output selection
system dependent
system depend-
ent
Mode
Cooling mode
Outdoor, Ext. switch,
both
-
Sensor
Switch input selection
-
-
Inverted
Inverted switching option
Yes, No
No
TDay off
Outdoor temperature cooling
20 … 40 °C
20 °C
Timer
Timer function cooling
Yes, No
No
tOn
Switch-on time cooling
00:00 … 23:45
00:00
tOff
Switch-off time cooling
00:00 … 23:45
00:00
Dew point
Dew point monitoring option
Humidity, Switch, Off
Off
Sensor
Sensor input selection
system dependent
system depend-
ent
Correction
Correction value
0 … 10 K
2 K
Emerg. shutd. Emergency shutdown option
Yes, No
No
Humidity
Relative humidity
5 … 100%
95%
Hysteresis
Re-energise hysteresis
1 … 10%
5%
Output
Output selection
system dependent
system depend-
ent
Holiday
Heating circuit off when holiday
function is active
Yes, No
No
Energy saving Energy saving operation option
Yes, No
No
Energy saving Energy saving operation submenu
-
-
Sen. return
HC return sensor allocation
system dependent
system depend-
ent
D
TOff
Switch-off temperature difference
energy saving operation
1 … 49 K
4 K
Break
Break time energy saving operation 0 … 60 min
15 min
Runtime
Runtime energy saving operation
0 … 60 min
2 min
Funct.
De/activation of the heating circuit
Activated, Deactivated,
Switch
Activated
Sensor
Switch input selection
-
-
Save func-
tion / Delete
function
Save or delete function
-
-