52
en
CS bypass
Solar / Opt. functions / Add new function / CS bypass
Adjustment
channel
Description
Adjustment range / se-
lection
Factory setting
Collector
Collector fi eld
system dependent
system depend-
ent
Irrad.
Switch-on irradiation
100 … 500 W / m²
200 W / m²
Delay
Delay time
10 … 300 s
120 s
Stmax off
Switch-on suppression
Yes, No
Yes
Funct.
Activation / Deactivation
Activated, Deactivated,
Switch
Activated
Sensor
Switch input selection
-
-
Save func-
tion / Delete
function
Save or delete function
-
-
This function is a further possibility to activate the solar circuit.
Note
To enable the use of the CS bypass function, a CS10 irradiation sensor has
to be connected.
When the CS bypass function is activated, the irradiation value is the switch-on
condition for the collector circuit.
The output switches on if the irradiation value is exceeded for the delay time. If
the irradiation falls below the adjusted irradiation value for the adjusted delay, the
output switches off.
If the switch-on suppression option off is activated, collector circuit activation will
be suppressed as long as all store temperatures are above their respective maxi-
mum temperatures.
Note
If both the CS bypass and the bypass function are activated, the CS bypass
will only affect the bypass. For this purpose, use S1 as the bypass sensor.
External heat exchanger
Solar / Opt. functions / Add new function / Ext. HX
Adjustment
channel
Description
Adjustment
range / selection
Factory setting
Output
Output selection
system dependent system dependent
Store
Store selection
system dependent all stores
Sensor HX
Reference sensor external heat
exchanger
system dependent system dependent
Target temp. Target temperature option
Yes, No
No
Sensor
Target temperature reference
sensor
system dependent system dependent
Targ. temp.
Target temperature
15 … 95 °C
60 °C
D
TOn
Switch-on temperature differ-
ence
1.0 … 20.0 K
10.0 K
D
TOff
Switch-off temperature differ-
ence
0.5 … 19.5 K
5.0 K
Overrun
Overrun time
0 … 15 min
2 min
Save func-
tion / Delete
function
Save or delete function
-
-
This function is used to link loading circuits that are separated by an external heat
exchanger.
The allocated output is energised if one of the selected stores is being loaded and
there is a temperature difference between the sensor of the corresponding store
and the reference sensor external heat exchanger.
Any number of the solar stores can be selected.
The output is switched off if this temperature difference falls below the adjusted
switch-off difference.
Note
In systems in which stores are equipped with their own loading pumps, the
heat exchanger relay controls the primary circuit pump.