66
en
Adjustment
channel
Description
Adjustment range / se-
lection
Factory setting
Sensor
Target temperature reference
sensor
system dependent
system dependent
Mixer
Mixer option
Yes, No
No
Mixer cl.
Output selection mixer closed
system dependent
system dependent
Mixer op.
Output selection mixer open
system dependent
system dependent
Sensor
Mixer sensor allocation
system dependent
system dependent
D
TOpen
Temperature difference mixer
open
0.5 … 30.0 K
5.0 K
D
TClosed
Temperature difference mixer
closed
0.0 … 29.5 K
2.0 K
Interval
Mixer interval
1 … 20 s
4 s
Funct.
Activation / Deactivation
Activated, Deactivat-
ed, Switch
Activated
Sensor
Switch input selection
-
-
Save func-
tion / Delete
function
Save or delete function
-
-
optional
Boiler sensor
Store sensor
Output
Mixer sensor
This function can be used for transferring heat from a solid fuel boiler to a store.
The allocated output is energised when all switch-on conditions are fulfi lled:
• the temperature difference between the allocated sensors has exceeded the
switch-on temperature difference
• the temperature difference between the allocated sensors has not fallen below
the switch-off temperature difference
• the temperature at the solid fuel boiler sensor has exceeded the minimum
temperature
• the temperature at the store sensor is below the maximum temperature
• one of the adjusted time frames is active (if the Timer option is selected)
When the set temperature difference is exceeded, pump speed control starts. For
every deviation by 1 / 10 of the adjusted rise value, the pump speed will be adjusted
by 1 %.
If the Target temp. option is activated, the pump speed control logic will change.
The controller will remain at the minimum pump speed until the temperature at the
allocated sensor exceeds the adjusted target temperature.
The Mixer option can be used to keep the boiler return temperature above TMin
boiler. The mixer will be controlled with the adjustable interval.
Return preheating
Arrangement / Opt. functions / Add new function / Ret. preheat.
Adjustment
channel
Description
Adjustment range / se-
lection
Factory setting
Output
Output selection
system dependent
system depend-
ent
Sen. return
Return sensor selection
system dependent
system depend-
ent
Sen. source
Heat source sensor selection
system dependent
system depend-
ent
D
TOn
Switch-on temperature differ-
ence
2.0 … 30.0 K
6.0 K
D
TOff
Switch-off temperature differ-
ence
1.0 … 29.0 K
4.0 K
Summer off
Summer switch-off option
Yes, No
No
Sensor
Outdoor sensor selection
system dependent
system depend-
ent
TOff
Switch-off temperature
10 … 60 °C
20 °C
Funct.
Activation / Deactivation
Activated, Deactivated,
Switch
Activated
Sensor
Switch input selection
-
-
Save func-
tion / Delete
function
Save or delete function
-
-
Summary of Contents for DeltaSol MX