77
en
When the Timer option is activated, a timer is indicated in which time frames for
the function can be adjusted. Outside these time frames, the adjusted room tem-
perature is decreased by the Correction value.
If the heating circuit is in cooling mode, the set room temperature is increased by
the Correction value.
Note
For information on timer adjustment see page 12.
To each room thermostat, an additional output can be allocated. The output switch-
es on when the temperature falls below the adjusted room temperature. This way,
the room in question can be excluded from the heating circuit via a valve as long as
the desired room temperature is reached.
Backup heating
For the backup heating of the heating circuit, 3 modes are available:
Therm.: In this mode, the set fl ow temperature is compared to a store reference
sensor.
Zone: In this mode, the set fl ow temperature is compared to 2 store reference
sensors. The switching conditions have to be fulfi lled at both reference sensors.
On/Off: In this mode, the backup heating is activated when the heating circuit
pump is switched on for heating.
In the Output submenu, the modes Standard and Demand are available. If
Standard is selected, the output can be adjusted.
If Demand is selected, a demand has to be activated and adjusted in the Heating
/ Shared rel. menu fi rst. If Adj. values is selected, the Heating / Shared rel. /
Demand menu will open.
In the correction mode Day/Off (see page 75) the heating circuit and the backup
heating is completely switched off during the night operation. The starting optimisa-
tion can be used for activating the backup heating before the day operation in order
to heat the store to a suffi ciently high temperature. The stopping optimisation can
be used for deactivating the backup heating before the start of the night operation.
If Solar off is activated, backup heating is suppressed when an adjusted store is
being loaded.