background image

en

5

Before flushing the system

 

Î

Disconnect the expansion vessel from the solar 
thermal system.

2.

 

Î

Connect the pressure hose of the filling and flush-
ing station to the fill valve (5) of the pump station.

 

Î

Connect the flushing hose of the filling and flush-
ing station to the drain valve (3) of the pump sta-
tion.

 

Î

Close the ball valve of the pump station (4).

 

Î

Open the fill valve (5) and the drain valve (3). 

 

Î

Switch on the filling pump of the filling and flush-
ing station.

 

Î

Flush the solar thermal system for at least 15 
minutes by means of the filling and flushing sta-
tion until the discharged solar fluid is free of gas 
bubbles and dirt particles.

 

Î

During flushing, bleed the solar thermal system 
several times until the discharged solar fluid (e. g. 
Tyfocor

®

, see chap. 11) is free of air bubbles.

 

Î

Open the ball valve of the pump station (4). 

After flushing the system

 

Î

Connect the expansion vessel to the solar ther-
mal system.

 

Î

Close the drain valve (3) of the pump station 
while the filling pump is running. 

BAR

 

Î

Increase system pressure (approx. 3.5 - 4 bar). The 
system pressure can be read from the pressure 
gauge.

 

Î

Close the fill valve (5).

 

Î

Switch off the filling pump.

 

Î

Check the pressure gauge to see whether the 
system pressure reduces and eliminate leaks 
where necessary.

 

Î

Slowly discharge the heat transfer fluid by means 
of the drain valve (3) until the operating pressure 
is set.

 

Î

Remove the hoses of the filling and flushing sta-
tion and screw the caps onto the fill and drain 
valves. Manually start the solar thermal pump at 
maximum speed (see controller manual) and let 
the fluid circulate for at least 15 minutes.

 

Î

Bleed the solar thermal system several times. 

 

Î

Check the system pressure at the pressure gauge.

11.

%

 

Î

Check the antifreeze ratio (not required if a 
ready-mix is used).

Ball valve positions

WARNING!

Scald danger! Damage by 
overpressure!
When the ball valve is closed, too 
high pressure may occur in the 
blocked-off line if it is heated.

 

Î

In order to prevent scald 
danger and damage by 
overpressure, make sure 
the blocked-off line is not 
heated.

Non-return valve in operating 
position, fluid flow in flow direc-
tion only.

Ball valve open, fluid flow in both 
directions possible.

Ball valve closed, no fluid flow.

Draining the system

 

Î

Open the ball valve (4).

 

Î

Open the air vent at the highest point of the sys-
tem (above the collectors).

 

Î

Open the drain valve.

Non-return valves

The non-return valves of the pump station are inte-
grated into the ball valves in flow and return and have 
an opening pressure of 20 mbar.
In order to completely drain the system, the non-
return valves have to be opened. 

 

Î

For this purpose, turn the handles of the ball 
valves by 45°.

 

Î

For normal system operation, open the ball valves 
completely.

Summary of Contents for FlowSol B HE WMZ

Page 1: ...his RESOL product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully www resol com Manual en Installation Operation Commissioning Manual for the specialised craftsman FlowSol B HE WMZ ...

Page 2: ...qualified per sonnel named by the manufacturer Contents 1 Overview 3 2 Mounting the station 4 3 Flushing and filling the solar system 4 4 Ball valve positions 5 5 Draining the system 5 6 Non return valves 5 7 Flow rate measurement 6 8 Air separator 6 9 Maintenance 6 10 Safety devices 6 11 Accessories 7 12 Information about the pump 7 13 Lists of spare parts 7 Description of symbols WARNING Warning...

Page 3: ...PWM2 12 power consumption of the pump 25W Safety valve 6 bar Pressure gauge 0 10bar Grundfos Direct Sensor VFS 1 12 VFS 2 40 Non return valves Opening pressure 20mbar openable Connection to diaphragm type expansion vessel ET flat sealing Outlet safety valve IT Connections to the solar pipes IT atVFS ET Maximum temperature flow return 120 C 95 C Maximum pressure 6 bar Medium Water with max 50 glyco...

Page 4: ...ween pump station and store and collector respectively Note All connections are already tightened such that they usually do not have to be tightened again However during commissioning of the system all connections have to be checked for leaks pressure test 3 Flushing and filling the solar system WARNING Scald danger Pressure surge damage If the medium enters strongly heat ed empty collectors press...

Page 5: ...e necessary Î Î Slowly discharge the heat transfer fluid by means of the drain valve 3 until the operating pressure is set Î Î Remove the hoses of the filling and flushing sta tion and screw the caps onto the fill and drain valves Manually start the solar thermal pump at maximum speed see controller manual and let the fluid circulate for at least 15 minutes Î Î Bleed the solar thermal system sever...

Page 6: ...n valve 3 If necessary open the union nut at the pressure side Î Î Now dismount the pump 10 Safety devices The pump station is equipped with a diaphragm safety valve which corresponds to the relevant directives and regulations For installation and operation please pay attention to the following advice The safety valve has to be easily accessible The ef ficiency of the valve must not be influenced ...

Page 7: ...ing and flushing station The SBS 2000 has been especially designed for pro fessionally filling and flushing solar thermal and heat ing systems Its many thought out details facilitate transport operation and cleaning the attractive de sign makes it the ideal companion for a professional performance Heat transfer fluids In our product portfolio you will find a range of heat transfer fluids for diffe...

Page 8: ...or the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false information and or the resulting damages Note The design and the specifications can be changed without notice The illustrations may differ from the original product Imprint This mounting and operation manual ...

Reviews: