FlowSol D / D HE
| 16
1
2
3
backward
SET
(selection-/
adjustment mode)
forward
12.2 Balance values
Maximum system pressure
Display of maximum system pressure since commissioning
or latest reset.
Minimum system pressure
Display of minimum system pressure since commissioning
or latest reset.
Maximum store temperature
Display of maximum store temperature (at the top, in °C)
since commissioning or latest reset.
Maximum power
Display of maximum power of the system (in kW) since
commissioning or latest reset.
Heat quantity
Display of heat yield in kWh and MWh respectively since
commissioning or latest reset.
Operating hours
Display of operating hours of the solar pump in h since
commissioning or latest reset.
Operating days
Display of operating days since commissioning.
2,4 bar
Max. pressure
1,5 bar
Min. pressure
20,4 kW
Max. power
94 °C
Max. upper storage
167
Operating days
16372 kWh
Heat
1075 h
Operating hours R1
The balance values can be reset in the balance and adjust-
ment menu.
Î
Keep button 3 pressed for 2 seconds. This changes the
display to show the balance values and adjustment values.
Î
Select the balance value which is to be reset with but-
tons 1 and 2 and briefly press button 3.
The value is then reset to 0.
13. Functions and options
Store loading
D
Ton
adjustment range 1,0 ... 25,0 K
factory setting 5,0 K
D
Toff
adjustment range 0,0 ... 24,0 K
factory setting 3,0 K
If the adjusted switch-on difference "
D
Ton“ between collec-
tor and store is exceeded, the store will be loaded. If this
difference falls below the adjusted switch-off difference
"
D
Toff“, the loading function will be switched off.
Loading of the store will also be switched-off or suppressed
if the collector is blocked (see collector minimum limitation)
or if the store is at maximum limitation.
Store maximum limitation
Tstmax
adjustment range 0 ... 90 °C
factory setting 60 °C
D
Tstmax
adjustment range 1,0 ... 10,0 K
factory setting 2,0 K
If the adjusted maximum temperature „Tstmax“ is exeeded,
the loading of the store is stopped. If the store cools down
by more than 2 K (hysteresis), the store will be loaded again.