PANEL ENROLLMENT (continued)
DSC ®
Translator enrollment:
Enter Wireless Enrollment mode.
Trip the translator cover tamper to enroll the translator.
Zone Type: 03
• For the first 24 hours after power-up, all translator
tamper trips will send a temporary “open” for
enrollment purposes.
Zone enrollment:
Enter Wireless Enrollment Mode.
Trip each zone to initiate enrollment.
Confirm ESN, Enter Zone #, and Zone Type.
Setup the zone for the desired behavior.
2GIG ®
Translator enrollment:
Enter RF enrollment mode
Sensor Type: (01) exit entry
Equipment Type: (1) contact
Equipment Code: (0862) DW10-345
At “Enter RF Serial Number”
•
Press SHIFT, Learn, then trip sensor
-or-
• Enter translator’s base ID number printed on the unit
Equipment Age: (0) new
Loop Number: (1)
Zone enrollment:
Enter RF enrollment mode.
Setup the zone for the desired behavior.
At “Enter RF Serial Number”
•
Press SHIFT, Learn, then trip sensor
-or-
• Enter zone ID number (translator’s base ID with the
last digit replaced with zone number 1-8).
Equipment Age: (0) new
Loop Number: (1)
Qolsys ®
• Qolsys IQ panel uses Interlogix 319.5MHz protocol.
• DSC Touch panel made by Qolsys uses DSC 433.92MHz
protocol.
FINISH
A
Close the cover. Test and verify proper operation at the
panel. Ensure all zone alarms are reported properly to the
central station.
B
Translator Locking: Locking the translator locks all
translator configuration settings and provides takeover
protection.
a) Ensure all zones are functioning as desired.
b) Carefully review the effects of translator locking before
proceeding:
• Translator can not be factory defaulted.
• Existing zone configurations can not be changed.
• Panel selection can not be changed.
• Translator
LOCKING CAN NOT BE UNDONE
.
c) Open the translator cover and cut the lock wire. The green
and red LED will flash, and the sounder will beep to
confirm.
C
With the cover closed, insert the cover securing screw into the
screw hole near the cover latch.
Notes
ZONES
• Powered zones have a 60 second lockout after power-up.
• Powered zones are turned off when the battery gets low.
• Powered zones have a four hour minimum battery backup after
power failure.
• Non-powered zones have 24-hours minimum battery backup
regardless of powered zones.
• All zone status is sent out within a couple minutes of the cover
being closed.
• If the translator loses both AC and battery backup power, zone
configuration data is retained.
• Low battery, tamper, and supervisory signals are reported by the
translator on its base zone with ID ending in “0”.
• Zone ID’s generally end in 1-8. This is NOT true for Honeywell
®
and powered zones.
• Low battery signals from the translator are suppressed in the first
24 hours after power-up. However, a missing battery condition is
reported right away.
FAULT CONDITIONS
• 12VDC output fault: Flashes and beeps every 10 seconds on the
green LED and sounder.
• 12VDC input overvoltage fault: Continually flashes and beeps on
the green LED and sounder.
• 12VDC input removed fault: Green LED turns off and the
sounder makes a long beep.
FACTORY DEFAULT
• To return the translator to a factory default condition, press and
hold the configure button. After a couple seconds, the sounder
will start beeping rapidly. Continue holding the button until the
sounder stops beeping.
• Factory default is not possible if the translator is locked.
ZONE TABLE
3
4
ZONE # SERIAL #
DESCRIPTION
0
Translator Base
1
2
3
4
5
6
7
8