ML Multistage Thermostat Installation Guide
www.resourcedm.com
Parameter Tables
No.
Parameter
Range
O
C (
O
F)
Default
Units
Description
P-01
Fans Mode
0 = Local
1 = Remote
2 = Man Off
3 = Man On
Local
Sets the Fans. Note the thermostat is
switched off when the fans are off.
See :
Remote GP Timer
P-02
Probe 3 Select
0 = Off
1 = Probe
2 = Probe with fault
3 = Probe with alarm
4 = Plant N/O
5 = Plant N/C
Off
Sets the function for input 3. If set to
“Plant” use a 0V return
P-03
Probe 4 Select
0 = Off
1 = Probe
2 = Probe with fault
3 = Probe with alarm
4 = Plant N/O
5 = Plant N/C
Off
Sets the function for input 3. If set to
“Plant” use a 0V return
P-04
Fans Run On
00:00 to 99:00
20:00
Mins:secs
Fans run-on for this period after the
timer goes off. Note: the thermostat is
off during this period.
P-11
Stat 1 Type
0 = Off
1 = Cooling
2 = Heating
Heating
Sets the thermostat stage function.
P-12
Stat 1 control weight
0
– 100%
50
%
Weighting is biased to Probe 1
P-13
Stat 1 cut-in
--60 to +60 / -76 to 140
15 / 59
O
C /
O
F
Heating relay is on below this set-
point. Cooling relay is off below this
set-point. *
P-14
Stat 1 diff
-60 to +60 / -76 to 140
1 / 1.8
O
C /
O
F
Heating relay goes off above this set-
point. Cooling relay goes off below this
set-point.*
P-15
Stat 1 alarm delay
00:00 to 99:00
20:00
Mins:secs
Time delay before the alarm occurs.
P-16
Stat 1 OT alarm
-60 to +60 / -76 to 140
30 / 86
O
C /
O
F
Over temperature alarm set-point
P-17
Stat 1 UT alarm
-60 to +60 / -76 to 140
-5 / 23
O
C /
O
F
Under temperature alarm set-point
P-21
Stat 2 Type
0 = Off
1 = Cooling
2 = Heating
Heating
Sets the thermostat stage function.
P-22
Stat 2 control weight
0
– 100%
50
%
Weighting is biased to Probe 1
P-23
Stat 2 cut-in
-60 to +60 / -76 to 140
18 / 64.4
O
C /
O
F
Heating relay is on below this set-
point. Cooling relay is off below this
set-point. *
P-24
Stat 2 diff
-60 to +60 / -76 to 140
1 / 1.8
O
C /
O
F
Heating relay goes off above this set-
point. Cooling relay goes off below this
set-point.*
P-25
Stat 2 alarm delay
00:00 to 99:00
20:00
Mins:secs
Time delay before the alarm occurs.
P-26
Stat 2 OT alarm
-60 to +60 / -76 to 140
30 / 86
O
C /
O
F
Over temperature alarm set-point
P-27
Stat 2 UT alarm
-60 to +60 / -76 to 140
-5 / 23
O
C /
O
F
Under temperature alarm set-point
P-31
Stat 3 Type
0 = Off
1 = Cooling
2 = Heating
Heating
Sets the thermostat stage function.
P-32
Stat 3 control weight
0
– 100%
50
%
Weighting is biased to Probe 1
P-33
Stat 3 cut-in
-60 to +60 / -76 to 140
20 / 68
O
C /
O
F
Heating relay is on below this set-
point. Cooling relay is off below this
set-point.*
P-34
Stat 3 diff
-60 to +60 / -76 to 140
1 / 1.8
O
C /
O
F
Heating relay goes off above this set-
point. Cooling relay goes off below this
set-point.*
P-35
Stat 3 alarm delay
00:00 to 99:00
20:00
Mins:secs
Time delay before the alarm occurs.
P-36
Stat 3 OT alarm
-60 to +60 / -76 to 140
30 / 86
O
C /
O
F
Over temperature alarm set-point
P-37
Stat 3 UT alarm
-60 to +60 / -76 to 140
-5 / 23
O
C /
O
F
Under temperature alarm set-point
P-41
Stat 4 Type
0 = Off
1 = Cooling
2 = Heating
Heating
Sets the thermostat stage function.
P-42
Stat 4 control weight
0
– 100%
50
%
Weighting is biased to Probe 1
P-43
Stat 4 cut-in
-60 to +60 / -76 to 140
22 / 71.6
O
C /
O
F
Heating relay is on below this set-
point. Cooling relay is off below this
set-point.*
P-44
Stat 4 diff
-60 to +60 / -76 to 140
1 / 1.8
O
C /
O
F
Heating relay goes off above this set-
point. Cooling relay goes off below this
set-point.*