DIRECTIONS FOR USE
AUTOMATIC STOP FILLING (1 LEVEL) FOR 7801.00 & 7803.00
OPERATION
On the 7801.00 & 7803.00 Cocoon bathtubs provided with the Rada Sense thermostatic mixer, the automatic stop filling is
made by the adjustment of the filling time.
For the model 7801.00 (R’GO shape tub), the filling time is pre-set at 5 minutes for a 27cm height of water level.
For the model 7803.00 (Key Hole shape tub), the filling time is pre-set at 7 minutes 15s for a 27cm height of water level.
The filling time can be modificated according to the needs.
AUTOMATIC STOP FILLING (1 LEVEL) FOR 7800.00 & 7802.00 (OPTION)
OPERATION
A capacitive sensor allows closing the filling valve of the bath; in this way it stops the water level automatically.
The sensor issues a magnetic field that is modified when water reaches it.
CONTROL PROCESS OF THE CAPACITIVE SENSORS :
1- Start filling the bath.
2- With the cleaning shower spray the inside surface of the bathtubs where is located the sensor.
To test a sensor, always use the shower and not the hand in order to be in use conditions.
3- When water from the shower is going to flow out the sensor, the filling valve must close (contact time: 2 seconds
minimum).
4- Start filling the bath.
5- Repeat the verification few times controlling :
- Closing of the valve
- Opening of the valve
6- Leave now the hi-lo bath fills up until the automatic stop.
7- Control the level.
8- Drain the bath. When the level will be reduced of few centimetres, stop draining and start filling.
ADJUSTMENT OF THE WATER LEVEL
It is possible to adjust the height of water level by moving the probe.
Contact Reval for more information.